Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 5, 2019, 07:37 AM
  • 02 1141_02 1140_04052019_005434.mp4

Date
04/05/2019
W/O
761209
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00351
PipeID
P02924
Time
12:37 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6514
Sewer Name
02 GARFIELD AVENUE EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_761209_TV02318_APR2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1141
Downstream MH
02 1140
Dir. of Survey
Downstream
Length Surveyed
316.2 ft.
Total Length
316.2 ft.
Structural Index
3
Structural Quick
514K
Structural Rating
371
O&M Index
2
O&M Quick
413L
O&M Rating
237
Overall Index
3
Overall Quick
Overall Rating
608
Pipe schematic from manhole 02 1141 to 02 1140
MH: 02 1141MH: 02 1140downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 11410 ft. MWM - Water Mark, 50 %of cross sectional area1 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start18.8 ft. RFJ - Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YESR18.8 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start24 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"65.3 ft. RFJ - Roots Fine Joint, from 01 to 04 o'clock, within 8 inches of joint: YESR72.5 ft. RFC - Roots Fine Connection, at 08 o'clock, within 8 inches of joint: YES72.5 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"75.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"108.6 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start116.1 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES126.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"146 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YES, Start176.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"210.3 ft. B - Crack, from 03 to 05 o'clock, within 8 inches of joint: YES - ROOTS FINE FROM 3'0 TO 9'0228.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"248.5 ft. TBI - Tap Break-In Intruding, at 02 o'clock, -, -, within 8 inches of joint: YES, 6", 1" - 50% BLOCKAGE, ROOTS248.5 ft. RML - Roots Medium Lateral, from 04 to 08 o'clock, 30 %, within 8 inches of joint: YES311.4 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Finish311.4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish311.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish316 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish316 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish316.2 ft. MGO - General Observation - CAPPED CONNECTION AT 3 O' CLOCK AT MH316.2 ft. AMH - Downstream Manhole, Survey Ends - 02 1140316.2 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH

Observation photos (9)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YESR

    18.8 ft. - Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YESR

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    18.8 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 01 to 04 o'clock, within 8 inches of joint: YESR

    65.3 ft. - Roots Fine Joint, from 01 to 04 o'clock, within 8 inches of joint: YESR

  • Roots Fine Connection, at 08 o'clock, within 8 inches of joint: YES

    72.5 ft. - Roots Fine Connection, at 08 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

    108.6 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

  • Crack, from 03 to 05 o'clock, within 8 inches of joint: YES - ROOTS FINE FROM 3'0 TO 9'0

    210.3 ft. - Crack, from 03 to 05 o'clock, within 8 inches of joint: YES - ROOTS FINE FROM 3'0 TO 9'0

  • Tap Break-In Intruding, at 02 o'clock, -, -, within 8 inches of joint: YES, 6", 1" - 50% BLOCKAGE, ROOTS

    248.5 ft. - Tap Break-In Intruding, at 02 o'clock, -, -, within 8 inches of joint: YES, 6", 1" - 50% BLOCKAGE, ROOTS

  • Roots Medium Lateral, from 04 to 08 o'clock, 30 %, within 8 inches of joint: YES

    248.5 ft. - Roots Medium Lateral, from 04 to 08 o'clock, 30 %, within 8 inches of joint: YES

Observations (29)

DistanceCodeObservation
248.5TBI50% BLOCKAGE, ROOTS
210.3BROOTS FINE FROM 3'0 TO 9'0
126.3TFC
146RFJ
18.8RFJ
24TFC
75.2TFC
3FM
18.8SSS
316.2MGOCAPPED CONNECTION AT 3 O' CLOCK AT MH
311.4RFJ
0MWL
316RFJ
116.1RFJ
1DAGS
72.5RFC
72.5TBA
311.4SSS
228.2TFC
108.6RFJ
176.9TFC
316.2AMH02 1140
316.2MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
316DAGS
311.5FM
65.3RFJ
0AMH02 1141
0MWM
248.5RML

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-04-05T00:37:11-07:00
documentation
PROPIPE
is_lateral_inspection
false