Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 10, 2019, 05:38 AM
  • 02 1158_02 1157_04092019_230306.mp4

Date
04/09/2019
W/O
761209
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00351
PipeID
P02942
Time
10:38 PM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5924
Sewer Name
02 GARFIELD AVENUE EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_761209_TV02318_APR2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
02 1158
Downstream MH
02 1157
Dir. of Survey
Downstream
Length Surveyed
285.9 ft.
Total Length
285.9 ft.
Structural Index
3
Structural Quick
4333
Structural Rating
25
O&M Index
2
O&M Quick
312J
O&M Rating
116
Overall Index
2
Overall Quick
Overall Rating
141
Pipe schematic from manhole 02 1158 to 02 1157
MH: 02 1158MH: 02 1157downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 11581 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start4.2 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start16.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES37.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES47.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"68.4 ft. CS - Crack Spiral, from 03 to 04 o'clock, within 8 inches of joint: YES88.7 ft. FM - Fracture Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES92.3 ft. FS - Fracture Spiral, from 01 to 04 o'clock, within 8 inches of joint: YES98.6 ft. RML - Roots Medium Lateral, from 09 to 10 o'clock, 30 %, within 8 inches of joint: YES99 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"103.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES116.4 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES137.1 ft. RFJ - Roots Fine Joint, from 04 to 05 o'clock, within 8 inches of joint: YES147.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"196 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"246.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"282 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish285 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish285.9 ft. AMH - Downstream Manhole, Survey Ends - 02 1157

Observation photos (10)

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    4.2 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    16.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    37.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 03 to 04 o'clock, within 8 inches of joint: YES

    68.4 ft. - Crack Spiral, from 03 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

    88.7 ft. - Fracture Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 01 to 04 o'clock, within 8 inches of joint: YES

    92.3 ft. - Fracture Spiral, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Roots Medium Lateral, from 09 to 10 o'clock, 30 %, within 8 inches of joint: YES

    98.6 ft. - Roots Medium Lateral, from 09 to 10 o'clock, 30 %, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    103.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    116.4 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 04 to 05 o'clock, within 8 inches of joint: YES

    137.1 ft. - Roots Fine Joint, from 04 to 05 o'clock, within 8 inches of joint: YES

Observations (22)

DistanceCodeObservation
99TF
116.4CL
137.1RFJ
246.9TFC
16.3FM
147.5TFC
0MWM
68.4CS
282DAGS
103.6CM
0MWL
0AMH02 1158
285FM
196TFA
92.3FS
88.7FM
37.4CM
98.6RML
1DAGS
47.7TFC
4.2FM
285.9AMH02 1157

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-04-09T22:38:41-07:00
documentation
PROPIPE
is_lateral_inspection
false