Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 5, 2019, 08:20 AM
  • 02 1139_02 1138_04052019_013554.mp4

Date
04/05/2019
W/O
761209
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00351
PipeID
P02922
Time
1:20 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6514
Sewer Name
02 GARFIELD AVENUE EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_761209_TV02318_APR2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1139
Downstream MH
02 1138
Dir. of Survey
Downstream
Length Surveyed
305.5 ft.
Total Length
305.5 ft.
Structural Index
4
Structural Quick
514J
Structural Rating
233
O&M Index
2
O&M Quick
412K
O&M Rating
129
Overall Index
3
Overall Quick
Overall Rating
362
Pipe schematic from manhole 02 1139 to 02 1138
MH: 02 1139MH: 02 1138downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 11390 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MWL - Water Level, 35 %of cross sectional area0.1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start15.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"16.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start28.2 ft. RFJ - Roots Fine Joint, at 03 o'clock, within 8 inches of joint: YESR69 ft. RFJ - Roots Fine Joint, from 01 to 04 o'clock, within 8 inches of joint: YESR83.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"84.3 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR, Start131.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"179.1 ft. RBL - Roots Ball Lateral, from 07 to 05 o'clock, 75 %, within 8 inches of joint: YES179.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"226.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"265.2 ft. B - Fracture, from 09 to 03 o'clock, within 8 inches of joint: YES270.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"289.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"302.6 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR, Finish302.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish305 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish305.5 ft. AMH - Downstream Manhole, Survey Ends - 02 1138305.5 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH

Observation photos (6)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    16.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, at 03 o'clock, within 8 inches of joint: YESR

    28.2 ft. - Roots Fine Joint, at 03 o'clock, within 8 inches of joint: YESR

  • Roots Fine Joint, from 01 to 04 o'clock, within 8 inches of joint: YESR

    69 ft. - Roots Fine Joint, from 01 to 04 o'clock, within 8 inches of joint: YESR

  • Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR, Start

    84.3 ft. - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR, Start

  • Roots Ball Lateral, from 07 to 05 o'clock, 75 %, within 8 inches of joint: YES

    179.1 ft. - Roots Ball Lateral, from 07 to 05 o'clock, 75 %, within 8 inches of joint: YES

  • Fracture, from 09 to 03 o'clock, within 8 inches of joint: YES

    265.2 ft. - Fracture, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (22)

DistanceCodeObservation
305DAGS
83.3TFC
179.1RBL
302.6RFJ
0AMH02 1139
0MWM
179.1TFA
131.3TFC
305.5AMH02 1138
69RFJ
305.5MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
15.4TFC
0MWL
226.9TFC
265.2B
16.6FM
270.6TFC
289.8TFC
28.2RFJ
302.6FM
84.3RFJ
0.1DAGS

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-04-05T01:20:50-07:00
documentation
PROPIPE
is_lateral_inspection
false