Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 8, 2019, 05:40 AM
  • 02 1587_02 1586 _08072019_225203.mp4

Date
08/07/2019
W/O
782707
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00231
PipeID
P18009
Time
10:40 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6737
Sewer Name
02 ARIZONA AVENUE TRUNK, SECTION 2
City
PROPIPE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_782707_TV02376_AUG2019
Sewer Type
Siphon
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1587
Downstream MH
02 1586
Dir. of Survey
Downstream
Length Surveyed
2.1 ft.
Total Length
2.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
5
O&M Quick
5141
O&M Rating
9
Overall Index
5
Overall Quick
Overall Rating
9
Pipe schematic from manhole 02 1587 to 02 1586
MH: 02 1587MH: 02 1586downstream0 ft. MGO - General Observation - WEST BARREL0 ft. MGO - General Observation - connection at 2'0 in mh0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 15870 ft. MWM - Water Mark, 50 %of cross sectional area2.1 ft. MSA - Survey Abandoned - SIPHON DOWNLEG2.1 ft. DSC - Deposits Settled Compacted, 95 %of cross sectional area, from 12 to 12 o'clock, , within 8 inches of joint: NO

Observation photos (2)

  • General Observation - WEST BARREL

    0 ft. - General Observation - WEST BARREL

  • Deposits Settled Compacted,  95 %of cross sectional area, from 12 to 12 o'clock,  , within 8 inches of joint: NO

    2.1 ft. - Deposits Settled Compacted, 95 %of cross sectional area, from 12 to 12 o'clock, , within 8 inches of joint: NO

Observations (7)

DistanceCodeObservation
0MGOWEST BARREL
2.1MSASIPHON DOWNLEG
2.1DSC
0MGOconnection at 2'0 in mh
0MWL
0AMH02 1587
0MWM

Properties (6)

additional_info
SC378236
custom_field_two
5
customer
LACSD
datetime
2019-08-07T22:40:57-07:00
documentation
PROPIPE
is_lateral_inspection
false