Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 26, 2019, 07:08 AM
  • 02 1545_02 1544A_26072019_001826.mp4

Date
07/26/2019
W/O
777333
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00230
PipeID
P03974
Time
12:08 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
6074
Sewer Name
02 ARIZONA AVENUE TRUNK, SECTION 1
City
LOS ANGELES
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
WO_777333_TV02007_JUL2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 1545
Downstream MH
02 1544A
Dir. of Survey
Downstream
Length Surveyed
137.5 ft.
Total Length
137.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
0
Overall Quick
Overall Rating
0
Pipe schematic from manhole 02 1545 to 02 1544A
MH: 02 1545MH: 02 1544Adownstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 15456.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"34 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"59 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"117.2 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - TAP ROOT137.5 ft. AMH - Downstream Manhole, Survey Ends - 02 1544A137.5 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH

Observation photos (1)

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - TAP ROOT

    117.2 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - TAP ROOT

Observations (9)

DistanceCodeObservation
6.7TF
137.5AMH02 1544A
34TF
59TBA
0MWL
0MWM
117.2TBTAP ROOT
137.5MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
0AMH02 1545

Properties (8)

additional_info
SC377944
custom_field_two
3
customer
LACSD
datetime
2019-07-26T00:08:01-07:00
documentation
PRO PIPE
is_lateral_inspection
false
lining
CIPP
year_laid
38526