Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 26, 2019, 08:21 AM
  • 05 1385_05 1384 _08262019_015942.mp4

Date
08/26/2019
W/O
782304
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00487
PipeID
P06605
Time
1:21 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6813
Sewer Name
05 MONETA TRUNK
City
GARDENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_782304_TV05336_AUG2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
05 1384
Downstream MH
05 1385
Dir. of Survey
Upstream
Length Surveyed
318.1 ft.
Total Length
318.1 ft.
Structural Index
4
Structural Quick
4200
Structural Rating
8
O&M Index
3
O&M Quick
3222
O&M Rating
10
Overall Index
3
Overall Quick
Overall Rating
18
Pipe schematic from manhole 05 1384 to 05 1385
MH: 05 1384MH: 05 1385upstream0 ft. AMH - Upstream Manhole, Survey Ends - 05 13850.4 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED0.4 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK2.3 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish3.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish3.5 ft. B - Broken, from 11 to 01 o'clock, within 8 inches of joint: YES40.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"86.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"192.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"235.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"252.5 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start253.4 ft. DAGS - Deposits Attached Grease, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES253.4 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish253.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"253.4 ft. RML - Roots Medium Lateral, at 02 o'clock, 10 %, within 8 inches of joint: YES295.7 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start305.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start318.1 ft. AMH - Downstream Manhole, Survey Begins - 05 1384318.1 ft. MWM - Water Mark, 40 %of cross sectional area318.1 ft. MWL - Water Level, 15 %of cross sectional area

Observation photos (6)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    12.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    22.4 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 20 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES

    64.7 ft. - Deposits Attached Grease, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES

  • Roots Medium Lateral, at 02 o'clock, 10 %, within 8 inches of joint: YES

    64.7 ft. - Roots Medium Lateral, at 02 o'clock, 10 %, within 8 inches of joint: YES

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    65.6 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Broken, from 11 to 01 o'clock, within 8 inches of joint: YES

    314.6 ft. - Broken, from 11 to 01 o'clock, within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
65.6DAGS
64.7DAGS
22.4DAGS
64.7DAGS
0AMH05 1384
0MWM
314.6FM
317.7MGOCONNECTION AT MH 9 O'CLOCK CAPPED
314.6B
231.9TFC
315.8DAGS
317.7MGOCONNECTION AT MH 3 O'CLOCK
64.7TFA
0MWL
82.5TFC
277.4TFC
318.1AMH05 1385
125.6TF
12.6FM
64.7RML

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-08-26T01:21:57-07:00
documentation
PRO PIPE
is_lateral_inspection
false