Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 19, 2019, 08:11 AM
  • 03 0038_03 0037_08192019_012933.mp4

Date
08/19/2019
W/O
782302
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00366
PipeID
P05058
Time
1:11 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6865
Sewer Name
03 LOS COYOTES DIAGONAL TRUNK
City
LAKEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_782302_TV03159_AUG2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
03 0038
Downstream MH
03 0037
Dir. of Survey
Downstream
Length Surveyed
325.8 ft.
Total Length
325.8 ft.
Structural Index
3
Structural Quick
3F00
Structural Rating
99
O&M Index
2
O&M Quick
2L00
O&M Rating
128
Overall Index
2
Overall Quick
Overall Rating
227
Pipe schematic from manhole 03 0038 to 03 0037
MH: 03 0038MH: 03 0037downstream0 ft. AMH - Upstream Manhole, Survey Begins - 03 00380 ft. MGO - General Observation - CONNECTION AT 3'0 IN MH0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start10.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"66.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"85.9 ft. CM - Crack Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES101.3 ft. CM - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES123.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"164.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"168.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start201.1 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"248 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"305.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"324 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish324 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish325.8 ft. MGO - General Observation - COCKROACHES IN MANHOLE325.8 ft. AMH - Downstream Manhole, Survey Ends - 03 0037

Observation photos (8)

  • Upstream Manhole, Survey Begins - 03 0038

    0 ft. - Upstream Manhole, Survey Begins - 03 0038

  • General Observation - CONNECTION AT 3'0 IN MH

    0 ft. - General Observation - CONNECTION AT 3'0 IN MH

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

    85.9 ft. - Crack Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

    101.3 ft. - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    168.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    325.8 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (20)

DistanceCodeObservation
0AMH03 0038
324DAGS
101.3CM
123.4TFA
0MGOCONNECTION AT 3'0 IN MH
0MGOCOCKROACHES IN MANHOLE
164.9TFA
305.4TFA
325.8MGOCOCKROACHES IN MANHOLE
10.5TFA
0MWL
325.8AMH03 0037
85.9CM
168.6CM
201.1TFA
66.9TFA
324CM
2DAGS
0MWM
248TBA

Properties (6)

additional_info
SC3783
custom_field_two
3
customer
LACSD
datetime
2019-08-19T01:11:35-07:00
documentation
PRO PIPE
is_lateral_inspection
false