Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 19, 2019, 11:24 AM
  • 01 1198_01 1155_08192019_043456.mp4

Date
08/19/2019
W/O
782260
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00226
PipeID
P02108
Time
4:24 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6867
Sewer Name
01 WILCOX AVENUE TRUNK, EXTENSION #1
City
SOUTH GATE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_782260_TV01250_AUG2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
16 in.
Width
16 in.
Upstream MH
01 1198
Downstream MH
01 1155
Dir. of Survey
Downstream
Length Surveyed
87.9 ft.
Total Length
87.9 ft.
Structural Index
3
Structural Quick
3B00
Structural Rating
42
O&M Index
2
O&M Quick
412B
O&M Rating
38
Overall Index
3
Overall Quick
Overall Rating
80
Pipe schematic from manhole 01 1198 to 01 1155
MH: 01 1198MH: 01 1155downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 11980 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start17 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start37.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"71 ft. MMC - Material Change, Cast Iron71 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish71 ft. SCP - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start87.9 ft. MGO - General Observation - COCKROACHES IN MANHOLE87.9 ft. SCP - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish87.9 ft. AMH - Downstream Manhole, Survey Ends - 01 115587.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish87.9 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3, 9, 12 O'CLOCK

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    17 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Material Change, Cast Iron

    71 ft. - Material Change, Cast Iron

  • Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    71 ft. - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    87.9 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (15)

DistanceCodeObservation
0AMH01 1198
17CM
0MGOCOCKROACHES IN MANHOLE
87.9MGOCOCKROACHES IN MANHOLE
0MWM
87.9SCP
37.1TFC
87.9AMH01 1155
71MMC
87.9DAGS
87.9MGOACTIVE CONNECTION AT MH 3, 9, 12 O'CLOCK
71CM
0MWL
2DAGS
71SCP

Properties (6)

additional_info
SC378337
custom_field_two
3
customer
LACSD
datetime
2019-08-19T04:24:11-07:00
documentation
PRO PIPE
is_lateral_inspection
false