- Date
- 08/15/2019
- W/O
- 782256
- Weather
- Dry
- Operator/Surveyor
- J. BUENROSTRO
- Sewer ID
- Z00973
- PipeID
- P02789
- Time
- 3:51 AM
- Certificate
- U-715-07000770
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K6752
- Sewer Name
- A JOINT OUTFALL A - UNIT 9
- City
- PARAMOUNT
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 02
- Page No.
- 31
- Purpose
- Routine Assessment
- Project
- RFIR_WO_782256_TV02134_AUG2019
- Sewer Type
- Siphon
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 42 in.
- Upstream MH
- A 1138
- Downstream MH
- A 1137
- Dir. of Survey
- Downstream
- Length Surveyed
- 2.7 ft.
- Total Length
- 2.7 ft.
- Structural Index
- 4
- Structural Quick
- 5131
- Structural Rating
- 8
- O&M Index
- 3
- O&M Quick
- 4121
- O&M Rating
- 6
- Overall Index
- 4
- Overall Quick
- —
- Overall Rating
- 14
Pipe schematic from manhole A 1138 to A 1137 Observation photos (3)

2.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: NO

2.6 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO

2.6 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: NO