Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 1, 2019, 05:25 AM
  • 02 1171_02 1170 _31072019_225643.mp4

Date
07/31/2019
W/O
776940
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00350
PipeID
P04565
Time
10:25 PM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5945
Sewer Name
02 GARFIELD AVENUE TRUNK
City
MONTELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_776940_TV02336_JUL2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
18 in.
Upstream MH
02 1171
Downstream MH
02 1170
Dir. of Survey
Downstream
Length Surveyed
301.1 ft.
Total Length
301.1 ft.
Structural Index
4
Structural Quick
4200
Structural Rating
8
O&M Index
3
O&M Quick
4122
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
16
Pipe schematic from manhole 02 1171 to 02 1170
MH: 02 1171MH: 02 1170downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 11710 ft. MWM - Water Mark, 60 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, at 03 o'clock, , within 8 inches of joint: YES7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES12.5 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start16.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"54.6 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start68.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"119.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"169.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"220.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"268.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"299.9 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish299.9 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish301.1 ft. AMH - Downstream Manhole, Survey Ends - 02 1170

Observation photos (10)

  • Deposits Attached Grease, 10 %of cross sectional area, at 03 o'clock,  , within 8 inches of joint: YES

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, at 03 o'clock, , within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    12.5 ft. - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    16.8 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    54.6 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    68.1 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    119.2 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    169.6 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    220.6 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    268.5 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (16)

DistanceCodeObservation
301.1AMH02 1170
119.2TFC
54.6DAGS
68.1TFC
268.5TF
220.6TFC
12.5FM
299.9DAGS
299.9FM
169.6TFC
0MWL
16.8TFC
0AMH02 1171
0MWM
2DAGS
7FM

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-07-31T22:25:47-07:00
documentation
PRO PIPE
is_lateral_inspection
false