Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 7, 2019, 04:36 PM
  • H 0406_H 0405_1072019_110136.mp4

Date
10/07/2019
W/O
0792740
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00177
PipeID
P10840
Time
9:36 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G8096
Sewer Name
H JOINT OUTFALL H - UNIT 5A
City
CITY OF INDUSTRY
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
02
Purpose
Capital Improvement Program Assesment
Project
20191007DF_JOINT_OUTFALL_H_UNIT_5A
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Upstream MH
H 0405
Downstream MH
H 0406
Dir. of Survey
Upstream
Length Surveyed
2.1 ft.
Total Length
2.1 ft.
Structural Index
3
Structural Quick
5131
Structural Rating
10
O&M Index
5
O&M Quick
5141
O&M Rating
9
Overall Index
4
Overall Quick
Overall Rating
19
Pipe schematic from manhole H 0405 to H 0406
MH: H 0405MH: H 0406upstream0 ft. MSA - Survey Abandoned - HIGH WATER0 ft. LU - Alignment Up, 45 %0.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES0.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES0.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES2 ft. MWM - Water Mark, 100 %of cross sectional area2 ft. MWL - Water Level, 100 %of cross sectional area2.1 ft. AMH - Downstream Manhole, Survey Begins - 10:15 AM

Observation photos (4)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Survey Abandoned - HIGH WATER

    2.1 ft. - Survey Abandoned - HIGH WATER

Observations (8)

DistanceCodeObservation
2SAP
2SSS
0.1MWM
0.1MWL
0AMH10:15 AM
2.1MSAHIGH WATER
2SRV
2.1LU

Properties (6)

additional_info
VIEW OF THE UPLEG FROM THE D/S SIPHON (SE BARREL)
custom_field_two
5
customer
LACSD
datetime
2019-10-07T09:36:16-07:00
documentation
FRANKLIN, IGNACIO, BRAR, SHADLER
is_lateral_inspection
false