Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 3, 2019, 10:54 AM
  • Section#1_17 0044_17 0043__1032019__I0261R.mp4

Date
10/03/2019
W/O
0793127
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00668
PipeID
P13766
Time
3:54 AM
Certificate
1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0261R
Sewer Name
17 DISTRICT #17 MAIN TRUNK
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 17
Page No.
06
Purpose
Maintenance Related
Project
20191003MDM_DISTRICT_17_MAIN_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
17 0043
Downstream MH
17 0044
Dir. of Survey
Upstream
Length Surveyed
171 ft.
Total Length
171 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3122
O&M Rating
9
Overall Index
2
Overall Quick
Overall Rating
9
Pipe schematic from manhole 17 0043 to 17 0044
MH: 17 0043MH: 17 0044upstream0 ft. AMH - Upstream Manhole, Survey Ends(COMPLETED REVERSE INSPECTION) - 4:15AM(COMPLETED REVERSE INSPECTION11 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - STUB12.3 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES - SLUDGE18 ft. MWL - Water Level, 20 %of cross sectional area30.1 ft. MGO - General Observation - LATERIALS 12:00 FINISH40.1 ft. MWM - Water Mark, 40 %of cross sectional area50.8 ft. TFD - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE 20% ROOTS50.8 ft. RML - Roots Medium Lateral, at 01 o'clock, 15 %, within 8 inches of joint: YES59 ft. RFL - Roots Fine Lateral, at 12 o'clock - 1%71.5 ft. RFL - Roots Fine Lateral, at 12 o'clock - 3%154.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - STUB START158.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - STUB162.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - STUB167 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - STUB171 ft. MWL - Water Level, 15 %of cross sectional area171 ft. AMH - Downstream Manhole, Survey Begins - 3:55AM171 ft. MWM - Water Mark, 30 %of cross sectional area

Observation photos (1)

  • Roots Medium Lateral, at 01 o'clock, 15 %, within 8 inches of joint: YES

    120.2 ft. - Roots Medium Lateral, at 01 o'clock, 15 %, within 8 inches of joint: YES

Observations (17)

DistanceCodeObservation
158.7DSZSLUDGE
12.8TFCSTUB
140.9MGOLATERIALS 12:00 FINISH
99.5RFL3%
0MWL
0AMH3:55AM
120.2TFDACTIVE 20% ROOTS
112RFL1%
160TFCSTUB
4TFCSTUB
153MWL
171AMH4:15AM(COMPLETED REVERSE INSPECTION
130.9MWM
120.2RML
0MWM
16.8TFCSTUB START
8.8TFCSTUB

Properties (5)

additional_info
PRE ROOT EVALUATION ONLY
customer
LACSD
datetime
2019-10-03T03:54:38-07:00
documentation
MARTIN,REVELES,OLIVER 111
is_lateral_inspection
false