Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 24, 2019, 08:52 AM
  • 32 0152_32 0151_09242019_015954.mp4

Date
09/24/2019
W/O
787630
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19903
Time
1:52 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7009
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_787630_TV32048_SEP2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 0152
Downstream MH
32 0151
Dir. of Survey
Downstream
Length Surveyed
150.8 ft.
Total Length
150.8 ft.
Structural Index
3
Structural Quick
3E2E
Structural Rating
145
O&M Index
2
O&M Quick
412E
O&M Rating
62
Overall Index
2
Overall Quick
Overall Rating
207
Pipe schematic from manhole 32 0152 to 32 0151
MH: 32 0152MH: 32 0151downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 01520 ft. MWL - Water Level, 15 %of cross sectional area2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start149.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish149.4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish149.4 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish150.8 ft. AMH - Downstream Manhole, Survey Ends - 32 0151150.8 ft. MGO - General Observation - COCKROACHES IN MANHOLE150.8 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK

Observation photos (3)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    150.8 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (12)

DistanceCodeObservation
149.4DAGS
150.8AMH32 0151
0MWM
2SSS
149.4SSS
0AMH32 0152
150.8MGOCOCKROACHES IN MANHOLE
2SAP
0MWL
2DAGS
150.8MGOACTIVE CONNECTION AT MH 9 O'CLOCK
149.4SAP

Properties (6)

additional_info
SC378625
custom_field_two
3
customer
LACSD
datetime
2019-09-24T01:52:48-07:00
documentation
PRO PIPE
is_lateral_inspection
false