Wastewater/Activity/PacpInspection/1.0Sep 20, 2019, 08:40 AM
  • 32 1216_32 1215 _09202019_020057.mp4

Date
09/20/2019
W/O
782704
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00843
PipeID
P19670
Time
1:40 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7006
Sewer Name
32 SOLEDAD CANYON RELIEF TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_782704_TV32023_AUG2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
32 1216
Downstream MH
32 1215
Dir. of Survey
Downstream
Length Surveyed
483.7 ft.
Total Length
483.7 ft.
Structural Index
3
Structural Quick
3R2R
Structural Rating
480
O&M Index
2
O&M Quick
412R
O&M Rating
196
Overall Index
2
Overall Quick
Overall Rating
676
Pipe schematic from manhole 32 1216 to 32 1215
MH: 32 1216MH: 32 1215downstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 12160 ft. MGO - General Observation - MAG COAT THROUGHOUT0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start280 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"483.7 ft. AMH - Downstream Manhole, Survey Ends - 32 1215483.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish483.7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish483.7 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • General Observation - MAG COAT THROUGHOUT

    0 ft. - General Observation - MAG COAT THROUGHOUT

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
483.7AMH32 1215
0AMH32 1216
280TBA
0MGOMAG COAT THROUGHOUT
2SAP
2DAGS
483.7DAGS
0MWL
483.7SSS
483.7SAP
0MWM
2SSS

Properties (7)

additional_info
SC378621
custom_field_two
3
customer
LACSD
datetime
2019-09-20T01:40:04-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
26787