Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 13, 2019, 07:32 AM
  • 18 0828_18 0827 _08132019_005604.mp4

Date
08/13/2019
W/O
782250
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z00707
PipeID
P14691
Time
12:32 AM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6778
Sewer Name
18 SO WHITTIER OUTFALL TR, SECT 5
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_782250_TV18119_AUG2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0827
Downstream MH
18 0828
Dir. of Survey
Upstream
Length Surveyed
241.3 ft.
Total Length
241.3 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 18 0827 to 18 0828
MH: 18 0827MH: 18 0828upstream0 ft. AMH - Upstream Manhole, Survey Ends - 18 08281.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish1.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Finish4.6 ft. CM - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish18.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"21.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"68.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"71.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"118.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"121 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"167.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"170.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"220.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"223.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"239.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start239.3 ft. CM - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start239.3 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start241.3 ft. MWM - Water Mark, 25 %of cross sectional area241.3 ft. AMH - Downstream Manhole, Survey Begins - 18 0827241.3 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
21.2TFC
0MWM
70.6TFC
18.1TFC
241.3AMH18 0828
239.6DAGS
120.3TFC
222.4TFC
0AMH18 0827
239.6DAE
73.8TFC
2DAGS
123.2TFC
236.7CM
2CM
2DAE
0MWL
169.8TFC
219.6TFC
173TFC

Properties (6)

additional_info
SC378284
custom_field_two
3
customer
LACSD
datetime
2019-08-13T00:32:15-07:00
documentation
PRO PIPE
is_lateral_inspection
false