Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 13, 2019, 05:58 AM
  • 18 0827_18 0826 _08122019_231652.mp4

Date
08/12/2019
W/O
782250
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z00707
PipeID
P14690
Time
10:58 PM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6778
Sewer Name
18 SO WHITTIER OUTFALL TR, SECT 5
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_782250_TV18119_AUG2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0827
Downstream MH
18 0826
Dir. of Survey
Downstream
Length Surveyed
96.4 ft.
Total Length
96.4 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
2211
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
10
Pipe schematic from manhole 18 0827 to 18 0826
MH: 18 0827MH: 18 0826downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 08270 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start2 ft. CS - Crack Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES7.3 ft. CM - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start34.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"37.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"83.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"87 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"91.8 ft. CM - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish94.6 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Finish94.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish96.1 ft. VC - Vermin Cockroach96.4 ft. AMH - Downstream Manhole, Survey Ends - 18 082696.4 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (4)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES

    2 ft. - Crack Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    7.3 ft. - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
83.7TFC
2DAE
94.6DAE
7.3CM
34.2TF
37.5TFC
2DAGS
87TFC
2CS
96.4AMH18 0826
96.4MGOCONNECTION AT MH 3 O'CLOCK
91.8CM
0AMH18 0827
0MWL
96.1VC
0MWM
94.6DAGS

Properties (6)

additional_info
SC378284
custom_field_two
3
customer
LACSD
datetime
2019-08-12T22:58:00-07:00
documentation
PRO PIPE
is_lateral_inspection
false