Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 29, 2017, 09:42 AM
  • 02 1683_02 1682_29062017_035737.mp4

Date
06/29/2017
W/O
613355
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00289
PipeID
P18840
Time
2:42 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3977-SC342140
Sewer Name
02 MONTEREY PARK EXTENSION TRUNK
City
MONTEREY PARK
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Routine Assessment
Project
WO_613355_TV02105_JUN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 1683
Downstream MH
02 1682
Dir. of Survey
Downstream
Length Surveyed
323.2 ft.
Total Length
323.2 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2L00
O&M Rating
128
Overall Index
2
Overall Quick
Overall Rating
131
Pipe schematic from manhole 02 1683 to 02 1682
MH: 02 1683MH: 02 1682downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 16833.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start26.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"100.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"175.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"190 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"244.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"276.7 ft. CM - Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES320.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish323.2 ft. AMH - Downstream Manhole, Survey Ends - 02 1682

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

    276.7 ft. - Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

Observations (12)

DistanceCodeObservation
190TF
0MWM
3.3DAGS
276.7CM
244.2TF
175.3TFC
0MWL
323.2AMH02 1682
26.6TFC
100.9TF
320.8DAGS
0AMH02 1683

Properties (4)

custom_field_two
3
customer
LACSD
datetime
2017-06-29T02:42:05-07:00
is_lateral_inspection
false