Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 3, 2017, 11:07 AM
  • 02 1676_02 1675_03072017_041845.mp4

Date
07/03/2017
W/O
613355
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00289
PipeID
P18833
Time
4:07 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3978-SC342141
Sewer Name
02 MONTEREY PARK EXTENSION TRUNK
City
MONTEREY PARK
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Routine Assessment
Project
WO_613355_TV02105_JUN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1676
Downstream MH
02 1675
Dir. of Survey
Downstream
Length Surveyed
165.4 ft.
Total Length
165.4 ft.
Structural Index
5
Structural Quick
5100
Structural Rating
5
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
4
Overall Quick
Overall Rating
11
Pipe schematic from manhole 02 1676 to 02 1675
MH: 02 1676MH: 02 1675downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 16760 ft. MWM - Water Mark, 50 %of cross sectional area3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start37.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"59.8 ft. B - Broken, from 02 to 05 o'clock, within 8 inches of joint: YES89.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"137.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"161.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish164.9 ft. MGO - General Observation - CONNECTION AT MH 3 OCLOCK165.4 ft. AMH - Downstream Manhole, Survey Ends - 02 1675

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Broken, from 02 to 05 o'clock, within 8 inches of joint: YES

    59.8 ft. - Broken, from 02 to 05 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
161.1DAGS
59.8B
3DAGS
164.9MGOCONNECTION AT MH 3 OCLOCK
137.4TFC
0MWL
0AMH02 1676
0MWM
37.8TFC
89.7TF
165.4AMH02 1675

Properties (4)

custom_field_two
3
customer
LACSD
datetime
2017-07-03T04:07:25-07:00
is_lateral_inspection
false