Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 4, 2018, 10:00 AM
  • C 0214_C 0213_642018_030705.mp4

Date
06/04/2018
W/O
0706820
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00124
PipeID
P09607
Time
3:00 AM
Certificate
U-014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0879
Sewer Name
C JOINT OUTFALL C - UNIT 3E
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
14
Purpose
Capital Improvement Program Assesment
Project
20180604MDM_JOINT_OUTFALL_C_UNIT_3E
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
C 0214
Downstream MH
C 0213
Dir. of Survey
Downstream
Length Surveyed
397 ft.
Total Length
397 ft.
Structural Index
2
Structural Quick
2600
Structural Rating
12
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
14
Pipe schematic from manhole C 0214 to C 0213
MH: C 0214MH: C 0213downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:10AM0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT2 ft. MGO - General Observation - MAG COAT 98% START 8:00 TO 4:0030.2 ft. SSS - Surface Spalling, from 01 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE46.6 ft. SSS - Surface Spalling, from 08 to 11 o'clock, within 8 inches of joint: NO - PELING CONCRETE58.8 ft. SSS - Surface Spalling, from 08 to 12 o'clock, within 8 inches of joint: YES - BLISTERING PEELING CONCRETE110 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - PEELED CONCRETE256 ft. SSS - Surface Spalling, from 08 to 11 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE342.8 ft. MGO - General Observation - 100% MAG COAT376.5 ft. SSS - Surface Spalling, from 11 to 03 o'clock, within 8 inches of joint: YES - BLISTERING CONCRETE396.3 ft. MGO - General Observation - 98% MAG COAT FINISH396.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE UNDER MAG COAT397 ft. AMH - Downstream Manhole, Survey Ends - 3:45AM

Observation photos (9)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

  • General Observation - MAG COAT 98% START 8:00 TO 4:00

    2 ft. - General Observation - MAG COAT 98% START 8:00 TO 4:00

  • Surface Spalling, from 01 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

    30.2 ft. - Surface Spalling, from 01 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

  • Surface Spalling, from 08 to 11 o'clock, within 8 inches of joint: NO - PELING CONCRETE

    46.6 ft. - Surface Spalling, from 08 to 11 o'clock, within 8 inches of joint: NO - PELING CONCRETE

  • Surface Spalling, from 08 to 12 o'clock, within 8 inches of joint: YES - BLISTERING PEELING CONCRETE

    58.8 ft. - Surface Spalling, from 08 to 12 o'clock, within 8 inches of joint: YES - BLISTERING PEELING CONCRETE

  • Deposits Settled Other,  10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES - PEELED CONCRETE

    110 ft. - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - PEELED CONCRETE

  • Surface Spalling, from 08 to 11 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

    256 ft. - Surface Spalling, from 08 to 11 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

  • General Observation - 100% MAG COAT

    342.8 ft. - General Observation - 100% MAG COAT

  • Surface Spalling, from 11 to 03 o'clock, within 8 inches of joint: YES - BLISTERING CONCRETE

    376.5 ft. - Surface Spalling, from 11 to 03 o'clock, within 8 inches of joint: YES - BLISTERING CONCRETE

Observations (15)

DistanceCodeObservation
396.3MGO98% MAG COAT FINISH
0MWM
46.6SSSPELING CONCRETE
376.5SSSBLISTERING CONCRETE
2SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
342.8MGO100% MAG COAT
396.3SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
0AMH3:10AM
2MGOMAG COAT 98% START 8:00 TO 4:00
256SSSBLISTERING CONCRETE
110DSZPEELED CONCRETE
58.8SSSBLISTERING PEELING CONCRETE
397AMH3:45AM
30.2SSSBLISTERING CONCRETE
0MWL

Properties (6)

custom_field_three
BLISTERING PEELING CONCRETE - 98% MAG COAT
custom_field_two
3
customer
LACSD
datetime
2018-06-04T03:00:19-07:00
documentation
MARTIN,REVELES,OLIVER 111,YOUNG
is_lateral_inspection
false