Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 1, 2018, 07:38 AM
  • 02 0035_02 0034_612018_005156.mp4

Date
06/01/2018
W/O
0707272
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00234
PipeID
P03067
Time
12:38 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0876
Sewer Name
02 ARTESIA EXTENSION TRUNK
City
BELLFLOWER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
39
Purpose
Routine Assessment
Project
20180601MDM_ARTESIA_EXTENSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0034
Downstream MH
02 0035
Dir. of Survey
Upstream
Length Surveyed
324.9 ft.
Total Length
324.9 ft.
Structural Index
2
Structural Quick
4232
Structural Rating
32
O&M Index
3
O&M Quick
3200
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
38
Pipe schematic from manhole 02 0034 to 02 0035
MH: 02 0034MH: 02 0035upstream0 ft. AMH - Upstream Manhole, Survey Ends - 1:45AM0.5 ft. FC - Fracture Circumferential, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish - 90% HAIRLINE AT JOINTS0.5 ft. FC - Fracture Circumferential, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish - 90% SLIGHT AT JOINTS0.5 ft. FL - Fracture Longitudinal, at 07 o'clock, within 8 inches of joint: YES, Finish - 20% SLIGHT AT JOINTS0.5 ft. MGO - General Observation - Conn. @ Mh, 12 O' Clock. Active0.5 ft. FL - Fracture Longitudinal, at 07 o'clock, within 8 inches of joint: YES, Finish - 20% HAIRLINE AT JOINTS57.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped59 ft. RPP - Repair Patch, from 01 to 04 o'clock, within 8 inches of joint: YES - CONCRETE60.1 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6", 6" - Open142.8 ft. RMJ - Roots Medium Joint, from 07 to 05 o'clock, 5 %, within 8 inches of joint: YESR145.4 ft. RMJ - Roots Medium Joint, from 03 to 05 o'clock, 5 %, within 8 inches of joint: YESR150.2 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open155.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped158.1 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped256.2 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped260 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped303.6 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL303.6 ft. FL - Fracture Longitudinal, at 07 TO 5 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS303.6 ft. FC - Fracture Circumferential, from 07 to 05 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS303.6 ft. FL - Fracture Longitudinal, at 07 TO 5 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS303.6 ft. FC - Fracture Circumferential, from 07 to 05 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS303.6 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL306.3 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL306.3 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL309.8 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL312.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL315.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT321.9 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - HAIRLINE321.9 ft. FC - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES - H324.9 ft. MWL - Water Level, 5 %of cross sectional area324.9 ft. MWM - Water Mark, 10 %of cross sectional area324.9 ft. AMH - Downstream Manhole, Survey Begins - 12:45AM

Observation photos (3)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT

    9.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL

    12.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL

  • Repair Patch, from 01 to 04 o'clock, within 8 inches of joint: YES - CONCRETE

    265.9 ft. - Repair Patch, from 01 to 04 o'clock, within 8 inches of joint: YES - CONCRETE

Observations (32)

DistanceCodeObservation
324.4FC90% HAIRLINE AT JOINTS
21.3FCSL
324.9AMH1:45AM
264.8TFOpen
21.3FLHAIRLINE AT JOINTS
174.7TBOpen
0MWL
324.4FC90% SLIGHT AT JOINTS
267.2TFCCapped
64.9TFCCapped
21.3FCSLIGHT AT JOINTS
3FCHAIRLINE
9.5FMSLIGHT
182.1RMJ
179.5RMJ
0MWM
324.4FL20% SLIGHT AT JOINTS
21.3FLSLIGHT AT JOINTS
324.4MGOConn. @ Mh, 12 O' Clock. Active
0AMH12:45AM
18.6FCSL
169.8TFCCapped
15.1FCSL
265.9RPPCONCRETE
18.6FCSL
12.2FMSL
3FCH
166.8TFCCapped
68.7TFCCapped
21.3FCHAIRLINE AT JOINTS
324.4FL20% HAIRLINE AT JOINTS
21.3FCSL

Properties (7)

additional_info
REVERSE INSPECTION
custom_field_three
SLIGHT HAIRLINE FRACTURES
custom_field_two
3
customer
LACSD
datetime
2018-06-01T00:38:40-07:00
documentation
MARTIN,REVELES,YOUNG
is_lateral_inspection
false