Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 29, 2017, 08:13 AM
  • H 0202_H 0201_6292017_013846.mp4

Date
06/29/2017
W/O
0647490
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00169
PipeID
P11226
Time
1:13 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0579
Sewer Name
H JOINT OUTFALL H - UNIT 2C
City
BELL GARDENS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
20
Purpose
Routine Assessment
Project
20170629MDM_JOINT_OUTFALL_H_UNIT_2C
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Upstream MH
H 0202
Downstream MH
H 0201
Dir. of Survey
Downstream
Length Surveyed
443.6 ft.
Total Length
443.6 ft.
Structural Index
2
Structural Quick
3325
Structural Rating
19
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
19
Pipe schematic from manhole H 0202 to H 0201
MH: H 0202MH: H 0201downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:20AM2 ft. MGO - General Observation - MAG COAT 95% START 8:00 TO 4:0014.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING CONCRETE UNDER MAG COAT19 ft. SSS - Surface Spalling, from 12 to 01 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING CONCRETE99.4 ft. SSS - Surface Spalling, from 11 to 12 o'clock, within 8 inches of joint: NO - FLAKING CONCRETE109.6 ft. SAV - Surface Aggregate Visible, from 09 to 11 o'clock, within 8 inches of joint: YES - SEVERE AGG SPORATIC147.5 ft. SSS - Surface Spalling, from 01 to 02 o'clock, within 8 inches of joint: NO - PEELING CONCRETE182.1 ft. MGO - General Observation - MAG COAT 99%308.4 ft. SSS - Surface Spalling, from 09 to 11 o'clock, within 8 inches of joint: NO - FLAKING CONCRETE399.7 ft. SAV - Surface Aggregate Visible, from 03 to 04 o'clock, within 8 inches of joint: NO, Start - SEVERE AGG399.7 ft. SAV - Surface Aggregate Visible, from 08 to 09 o'clock, within 8 inches of joint: NO, Start - SEVERE AGG408.4 ft. SAV - Surface Aggregate Visible, from 08 to 09 o'clock, within 8 inches of joint: NO, Finish - SEVERE AGG408.4 ft. SAV - Surface Aggregate Visible, from 03 to 04 o'clock, within 8 inches of joint: NO, Finish - SEVERE AGG443 ft. MGO - General Observation - MAG COAT 95% FINISH443 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING,PEELING,FLAKING CONCRETE443.6 ft. AMH - Downstream Manhole, Survey Ends - 2:1OAM

Observation photos (10)

  • General Observation - MAG COAT 95% START 8:00 TO 4:00

    2 ft. - General Observation - MAG COAT 95% START 8:00 TO 4:00

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING CONCRETE  UNDER MAG COAT

    14.1 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING CONCRETE UNDER MAG COAT

  • Surface Spalling, from 12 to 01 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING CONCRETE

    19 ft. - Surface Spalling, from 12 to 01 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING CONCRETE

  • Surface Spalling, from 11 to 12 o'clock, within 8 inches of joint: NO - FLAKING CONCRETE

    99.4 ft. - Surface Spalling, from 11 to 12 o'clock, within 8 inches of joint: NO - FLAKING CONCRETE

  • Surface Aggregate Visible, from 09 to 11 o'clock, within 8 inches of joint: YES - SEVERE AGG SPORATIC

    109.6 ft. - Surface Aggregate Visible, from 09 to 11 o'clock, within 8 inches of joint: YES - SEVERE AGG SPORATIC

  • Surface Spalling, from 01 to 02 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    147.5 ft. - Surface Spalling, from 01 to 02 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

  • General Observation - MAG COAT 99%

    182.1 ft. - General Observation - MAG COAT 99%

  • Surface Spalling, from 09 to 11 o'clock, within 8 inches of joint: NO - FLAKING CONCRETE

    308.4 ft. - Surface Spalling, from 09 to 11 o'clock, within 8 inches of joint: NO - FLAKING CONCRETE

  • Surface Aggregate Visible, from 03 to 04 o'clock, within 8 inches of joint: NO, Start - SEVERE AGG

    399.7 ft. - Surface Aggregate Visible, from 03 to 04 o'clock, within 8 inches of joint: NO, Start - SEVERE AGG

  • Surface Aggregate Visible, from 08 to 09 o'clock, within 8 inches of joint: NO, Start - SEVERE AGG

    399.7 ft. - Surface Aggregate Visible, from 08 to 09 o'clock, within 8 inches of joint: NO, Start - SEVERE AGG

Observations (18)

DistanceCodeObservation
308.4SSSFLAKING CONCRETE
443MGOMAG COAT 95% FINISH
0MWL
19SSSBLISTERING FLAKING CONCRETE
443SSSBLISTERING,PEELING,FLAKING CONCRETE
0MWM
99.4SSSFLAKING CONCRETE
0AMH1:20AM
14.1SSSBLISTERING CONCRETE UNDER MAG COAT
109.6SAVSEVERE AGG SPORATIC
399.7SAVSEVERE AGG
182.1MGOMAG COAT 99%
399.7SAVSEVERE AGG
443.6AMH2:1OAM
408.4SAVSEVERE AGG
408.4SAVSEVERE AGG
2MGOMAG COAT 95% START 8:00 TO 4:00
147.5SSSPEELING CONCRETE

Properties (6)

custom_field_three
SEVERE AGG SPORATIC-95% MAG COAT ON PIPE
custom_field_two
3
customer
LACSD
datetime
2017-06-29T01:13:06-07:00
documentation
MARTIN,MANANES,OLIVER 111
is_lateral_inspection
false