Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 13, 2017, 08:26 AM
  • 05 1716_05 1715_2132017_003716.mp4

Date
02/13/2017
W/O
0607779
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00471
PipeID
P06943
Time
12:26 AM
Certificate
1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
HO440
Sewer Name
LOMITA TRUNK
City
LOMITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
32
Purpose
Capital Improvement Program Assesment
Project
20170210MDM_LOMITA_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
05 1716
Downstream MH
05 1715
Dir. of Survey
Downstream
Length Surveyed
311.6 ft.
Total Length
311.6 ft.
Structural Index
2
Structural Quick
342F
Structural Rating
84
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
88
Pipe schematic from manhole 05 1716 to 05 1715
MH: 05 1716MH: 05 1715downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:35AM0 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. FS - Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES, Start - SLIGHT2 ft. FS - Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES, Start - SLIGHT27.6 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SL30.5 ft. FS - Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES - SL34.5 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - H37.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active41.9 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL41.9 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - SL70.4 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - SL70.4 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - SL78.3 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H84.3 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - SL105.3 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H108.8 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - H108.8 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H127.6 ft. FS - Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES - SLIGHT140.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open143 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SL145.5 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - SL145.5 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - SL148.6 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - H148.6 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H152.8 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H154.7 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - SL165.5 ft. MWL - Water Level, 10 %of cross sectional area165.5 ft. MWM - Water Mark, 30 %of cross sectional area196 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SL233.3 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - H261.3 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL261.4 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H263.5 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - H263.5 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H266.6 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H269.9 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL269.9 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - SL272.8 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL272.8 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SL279.6 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL282.6 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H282.6 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL286.3 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL289.2 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H292.2 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H307.7 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL311.3 ft. FS - Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES, Finish - SLIGHT311.3 ft. FS - Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES, Finish - SLIGHT311.3 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active311.3 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. OPEN311.6 ft. AMH - Downstream Manhole, Survey Ends - 1:25AM

Observation photos (5)

  • Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    2 ft. - Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    2 ft. - Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES - SL

    30.5 ft. - Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES - SL

  • Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES - SLIGHT

    127.6 ft. - Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES - SLIGHT

  • Water Mark, 30 %of cross sectional area

    165.5 ft. - Water Mark, 30 %of cross sectional area

Observations (52)

DistanceCodeObservation
140.7TFOpen
269.9FCSL
127.6FSSLIGHT
266.6FCH
272.8FCSL
0MWL
311.3FSSLIGHT
282.6FCH
269.9FCSL
261.4FCH
84.3FCSL
145.5FCSL
311.3FSSLIGHT
311.6AMH1:25AM
41.9FCSL
34.5FCH
70.4FCSL
105.3FCH
2FSSLIGHT
307.7FCSL
165.5MWL
282.6FCSL
37.3TFActive
30.5FSSL
292.2FCH
263.5FCH
108.8FCH
41.9FCSL
145.5FCSL
311.3MGOConn. @ Mh, 3 O' Clock. Active
0AMH12:35AM
261.3FCSL
108.8FCH
233.3FCH
148.6FCH
27.6FCSL
272.8FCSL
196FCSL
143FCSL
2FSSLIGHT
311.3MGOConn. @ Mh, 9 O' Clock. OPEN
263.5FCH
148.6FCH
78.3FCH
286.3FCSL
165.5MWM
154.7FCSL
279.6FCSL
70.4FCSL
152.8FCH
0MWM
289.2FCH

Properties (6)

custom_field_three
SLIGHT SPRIAL JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2017-02-13T00:26:07-08:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false