Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 11, 2016, 08:41 PM
  • 30 0268_30 0267_2112016_125602.mp4

Date
02/11/2016
W/O
0541792
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00876
PipeID
P17964
Time
12:41 PM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7049
Sewer Name
30 PLAZA TRUNK
City
PALOS VERDES
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 30
Page No.
09
Purpose
Routine Assessment
Project
20160211AM_PLAZA_TRUNK
Material
NRCP
Shape
Circular
Height
10 in.
Upstream MH
30 0268
Downstream MH
30 0267
Dir. of Survey
Downstream
Length Surveyed
84.7 ft.
Total Length
84.7 ft.
Structural Index
3
Structural Quick
5443
Structural Rating
47
O&M Index
3
O&M Quick
3121
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
52
Pipe schematic from manhole 30 0268 to 30 0267
MH: 30 0268MH: 30 0267downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:00 PM0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start4.1 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES7.1 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES7.1 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES20.4 ft. FM - Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES25.3 ft. TBD - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: YES, 6" - UNKOWN, BROKEN, 95% ROOTS29.6 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES30 ft. FM - Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES39.8 ft. B - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES40.6 ft. SMW - Surface Missing Wall, from 09 to 03 o'clock, within 8 inches of joint: YES40.6 ft. MGP - General Photograph - BROKEN PIPE40.6 ft. MGP - General Photograph - MISSING WALL59.6 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE, BROKEN, 40% ROOTS59.7 ft. MGP - General Photograph - BROKEN CONN.61.2 ft. SMW - Surface Missing Wall, from 09 to 11 o'clock, within 8 inches of joint: YES61.2 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start61.2 ft. B - Broken, from 10 to 04 o'clock, within 8 inches of joint: YES64.6 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Finish79.4 ft. FM - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES82.5 ft. MGO - General Observation - CHIPPING THROUGHOUT THE REACH82.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish82.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish82.5 ft. MGO - General Observation - SLIGHT GREASE THROUGHOUT THE REACH84.7 ft. AMH - Downstream Manhole, Survey Ends - 1:20 PM

Observation photos (14)

  • Water Level, 10 %of cross sectional area

    0 ft. - Water Level, 10 %of cross sectional area

  • Upstream Manhole, Survey Begins - 1:00 PM

    0 ft. - Upstream Manhole, Survey Begins - 1:00 PM

  • Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

    20.4 ft. - Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

  • Tap Break-In Defective, at 02 o'clock, -,  , within 8 inches of joint: YES, 6" - UNKOWN, BROKEN, 95% ROOTS

    25.3 ft. - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: YES, 6" - UNKOWN, BROKEN, 95% ROOTS

  • Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    30 ft. - Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Broken, from 08 to 04 o'clock, within 8 inches of joint: YES

    39.8 ft. - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Surface Missing Wall, from 09 to 03 o'clock, within 8 inches of joint: YES

    40.6 ft. - Surface Missing Wall, from 09 to 03 o'clock, within 8 inches of joint: YES

  • General Photograph - BROKEN PIPE

    40.6 ft. - General Photograph - BROKEN PIPE

  • General Photograph - MISSING WALL

    40.6 ft. - General Photograph - MISSING WALL

  • Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE, BROKEN, 40% ROOTS

    59.6 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE, BROKEN, 40% ROOTS

  • General Photograph - BROKEN CONN.

    59.7 ft. - General Photograph - BROKEN CONN.

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start

    61.2 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start

  • Broken, from 10 to 04 o'clock, within 8 inches of joint: YES

    61.2 ft. - Broken, from 10 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    79.4 ft. - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

Observations (28)

DistanceCodeObservation
82.5MGOCHIPPING THROUGHOUT THE REACH
61.2SMW
0MWL
64.6CL
7.1CL
61.2CL
7.1CL
0AMH1:00 PM
61.2B
2SSS
82.5SAV
30FM
84.7AMH1:20 PM
20.4FM
40.6SMW
59.6TFDACTIVE, BROKEN, 40% ROOTS
40.6MGPBROKEN PIPE
4.1CL
59.7MGPBROKEN CONN.
79.4FM
40.6MGPMISSING WALL
82.5SSS
39.8B
25.3TBDUNKOWN, BROKEN, 95% ROOTS
2SAV
0MWM
29.6CL
82.5MGOSLIGHT GREASE THROUGHOUT THE REACH

Properties (6)

custom_field_three
BROKEN PIPE, FRACTURES, CHIPPING THROUGHOUT
custom_field_two
1
customer
LACSD
datetime
2016-02-11T12:41:50-08:00
documentation
MIRANDA, SHADLER, MIRABAL, FRANKLIN
is_lateral_inspection
false