Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 31, 2016, 07:36 AM
  • 16 0340_16 0339_10312016_005036.mp4

Date
10/31/2016
W/O
0596965
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00665
PipeID
P13391
Time
12:36 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6757
Sewer Name
16 SAN MARINO OUTFALL TRUNK
City
SAN MARINO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
17
Purpose
Capital Improvement Program Assesment
Project
20161031MDM_SAN_MARINO_OUTFALL_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
16 in.
Upstream MH
16 0340
Downstream MH
16 0339
Dir. of Survey
Downstream
Length Surveyed
300.7 ft.
Total Length
300.7 ft.
Structural Index
2
Structural Quick
342B
Structural Rating
42
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
42
Pipe schematic from manhole 16 0340 to 16 0339
MH: 16 0340MH: 16 0339downstream0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:40AM10.6 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - SLIGHT12.9 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - HAIRLINE15.1 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H15.1 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - H20.7 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SL28.4 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H28.4 ft. FC - Fracture Circumferential, from 09 to 01 o'clock, within 8 inches of joint: YES - SL30.7 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - SL30.7 ft. FC - Fracture Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES - SL33.5 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SL35 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped36.2 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL36.2 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - H43.8 ft. FL - Fracture Longitudinal, at 08 TO 4 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS43.8 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SL43.8 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS43.8 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS43.8 ft. FL - Fracture Longitudinal, at 08 TO 4 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS106.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open175.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped202.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT208.5 ft. MGP - General Photograph - LONG FRACTURE218.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SLIGHT226.5 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - MODERATE244.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped300.3 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 60% SLIGHT300.3 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 20% SLIGHT300.3 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 20% HAIRLINE300.3 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 50% HAIRLINE300.7 ft. AMH - Downstream Manhole, Survey Ends - 1:25AM

Observation photos (3)

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    202.8 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • General Photograph - LONG FRACTURE

    208.5 ft. - General Photograph - LONG FRACTURE

  • Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - MODERATE

    226.5 ft. - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - MODERATE

Observations (34)

DistanceCodeObservation
218.1FLSLIGHT
33.5FCSL
10.6FLSLIGHT
244.8TFCCapped
43.8FLHAIRLINE AT JOINTS
36.2FCSL
0MGOConn. @ Mh, 9 O' Clock. Active
43.8FCSL
300.7AMH1:25AM
0MWL
30.7FCSL
43.8FCSLIGHT AT JOINTS
28.4FCH
0MWM
30.7FCSL
226.5FCMODERATE
20.7FCSL
0AMH12:40AM
300.3FC60% SLIGHT
300.3FL20% SLIGHT
12.9FCHAIRLINE
28.4FCSL
175.5TFCCapped
106.4TFOpen
300.3FL20% HAIRLINE
36.2FCH
43.8FCHAIRLINE AT JOINTS
202.8FLSLIGHT
300.3FC50% HAIRLINE
208.5MGPLONG FRACTURE
43.8FLSLIGHT AT JOINTS
15.1FCH
35TFCCapped
15.1FCH

Properties (6)

custom_field_three
SLIGHT LONG FRACTURE JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2016-10-31T00:36:13-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false