Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 29, 2016, 04:21 PM
  • C 0653_C 0652_10292016_093650.mp4

Date
10/29/2016
W/O
0596967
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00266
PipeID
P23919
Time
9:21 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7262
Sewer Name
C JOINT OUTFALL C - UNIT 3F
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
15
Purpose
Routine Assessment
Project
20161029AM_JOINT_OUTFALL_C_UNIT_3F
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
C 0653
Downstream MH
C 0652
Dir. of Survey
Downstream
Length Surveyed
310.1 ft.
Total Length
310.1 ft.
Structural Index
3
Structural Quick
4336
Structural Rating
33
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
33
Pipe schematic from manhole C 0653 to C 0652
MH: C 0653MH: C 0652downstream0 ft. MGO - General Observation - ROACHES INSIDE THE MH.0 ft. AMH - Upstream Manhole, Survey Begins - 9:36 AM0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area14.2 ft. JSM - Joint Separated Medium18.9 ft. MGO - General Observation - CHIPPING59.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES59.8 ft. JSM - Joint Separated Medium81 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES97.9 ft. FM - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN101.7 ft. JSM - Joint Separated Medium101.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES139 ft. CM - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES147.2 ft. CM - Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES155.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start196.4 ft. FM - Fracture Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES266.1 ft. MWL - Water Level, 25 %of cross sectional area274.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES306.9 ft. MGO - General Observation - SEPARATED JOINTS THROUGHOUT THE REACH307.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish309.9 ft. MGO - General Observation - ROACHES INSIDE THE MH.310.1 ft. AMH - Downstream Manhole, Survey Ends - 10:03 AM, PIPE DROPS INTO THE MH.310.1 ft. MGO - General Observation - SLIGHT GREASE/OIL THROUGHOUT THE REACH

Observation photos (10)

  • Joint Separated Medium

    14.2 ft. - Joint Separated Medium

  • General Observation - CHIPPING

    18.9 ft. - General Observation - CHIPPING

  • Joint Separated Medium

    59.8 ft. - Joint Separated Medium

  • Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

    97.9 ft. - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    155.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

    196.4 ft. - Fracture Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    274.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • General Observation - SEPARATED JOINTS THROUGHOUT THE REACH

    306.9 ft. - General Observation - SEPARATED JOINTS THROUGHOUT THE REACH

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

    307.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

  • Downstream Manhole, Survey Ends - 10:03 AM, PIPE DROPS INTO THE MH.

    310.1 ft. - Downstream Manhole, Survey Ends - 10:03 AM, PIPE DROPS INTO THE MH.

Observations (23)

DistanceCodeObservation
18.9MGOCHIPPING
139CM
274.6FM
0MGOROACHES INSIDE THE MH.
266.1MWL
0AMH9:36 AM
147.2CM
0MWM
196.4FM
59.8CM
306.9MGOSEPARATED JOINTS THROUGHOUT THE REACH
101.7JSM
310.1AMH10:03 AM, PIPE DROPS INTO THE MH.
0MWL
155.5CM
307.2CM
59.8JSM
81CM
310.1MGOSLIGHT GREASE/OIL THROUGHOUT THE REACH
101.7CM
309.9MGOROACHES INSIDE THE MH.
97.9FMPOSSIBLY BROKEN
14.2JSM

Properties (7)

custom_field_three
POSSIBLE BROKEN PIPE
custom_field_two
2
customer
LACSD
datetime
2016-10-29T09:21:25-07:00
documentation
MIRANDA, SHADLER, BRAR
is_lateral_inspection
false
year_laid
20020814