Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 27, 2016, 09:29 AM
  • 16 0101_16 0100_10272016_025638.mp4

Date
10/27/2016
W/O
0596906
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00641
PipeID
P13139
Time
2:29 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6751
Sewer Name
16 ALLEN AVENUE TRUNK, SECTION 5
City
SAN MARINO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
14
Purpose
Routine Assessment
Project
20161025MDM_ALLEN_AVENUE_TRUNK_SECTION_5
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
16 0101
Downstream MH
16 0100
Dir. of Survey
Downstream
Length Surveyed
379.7 ft.
Total Length
379.7 ft.
Structural Index
3
Structural Quick
3522
Structural Rating
19
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
19
Pipe schematic from manhole 16 0101 to 16 0100
MH: 16 0101MH: 16 0100downstream0 ft. AMH - Upstream Manhole, Survey Begins - 2:55AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. MGO - General Observation - MAG COAT 40% START 8:00 TO 4:002 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING LAITANCE COAT2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG23.9 ft. MGO - General Observation - MAG COAT 80% START55.2 ft. SSS - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: NO - B EGINNING PEELING CONCRETE78.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG83.5 ft. MGO - General Observation - MAG COAT 50% START86.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG266.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - VERE AGG321.2 ft. SAP - Surface Aggregate Projecting, from 02 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG379.1 ft. MGO - General Observation - MAG COAT 50% FINISH379.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - PEELING LAITANCE COAT379.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG379.7 ft. AMH - Downstream Manhole, Survey Ends - 3:30AM

Observation photos (9)

  • General Observation - MAG COAT 40% START 8:00 TO 4:00

    2 ft. - General Observation - MAG COAT 40% START 8:00 TO 4:00

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING LAITANCE COAT

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING LAITANCE COAT

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • General Observation - MAG COAT 80% START

    23.9 ft. - General Observation - MAG COAT 80% START

  • Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: NO - B EGINNING PEELING CONCRETE

    55.2 ft. - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: NO - B EGINNING PEELING CONCRETE

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

    78.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    86.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - VERE AGG

    266.8 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - VERE AGG

  • Surface Aggregate Projecting, from 02 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

    321.2 ft. - Surface Aggregate Projecting, from 02 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

Observations (17)

DistanceCodeObservation
379.1MGOMAG COAT 50% FINISH
0AMH2:55AM
379.7AMH3:30AM
266.8SAVVERE AGG
0MWL
78.6SAVSEVERE AGG
23.9MGOMAG COAT 80% START
0MWM
2MGOMAG COAT 40% START 8:00 TO 4:00
55.2SSSB EGINNING PEELING CONCRETE
83.5MGOMAG COAT 50% START
321.2SAPSEVERE AGG
2SSSPEELING LAITANCE COAT
86.5SAVSEVERE AGG
379.1SSSPEELING LAITANCE COAT
379.1SAVSEVERE AGG
2SAVSEVERE AGG

Properties (6)

custom_field_three
PEELING LAITANCE COAT-VISIBLE SEVERE AGG
custom_field_two
3
customer
LACSD
datetime
2016-10-27T02:29:45-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false