Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 27, 2016, 07:34 AM
  • 16 0104_16 0103_10272016_004430.mp4

Date
10/27/2016
W/O
0596906
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00641
PipeID
P13142
Time
12:34 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6751
Sewer Name
16 ALLEN AVENUE TRUNK, SECTION 5
City
SAN MARINO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
14
Purpose
Routine Assessment
Project
20161025MDM_ALLEN_AVENUE_TRUNK_SECTION_5
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
16 0103
Downstream MH
16 0104
Dir. of Survey
Upstream
Length Surveyed
21.7 ft.
Total Length
21.7 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 16 0103 to 16 0104
MH: 16 0103MH: 16 0104upstream0 ft. AMH - Upstream Manhole, Survey Ends - 12:45AM0.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - PEELING - FLAKING CONCRETE0.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG0.3 ft. MGO - General Observation - MAG COAT 30% FINISH19.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG19.7 ft. MGO - General Observation - MAG COAT 30% 8:00 TO 4:00 START19.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING-FLAKING CONCRETE21.7 ft. AMH - Downstream Manhole, Survey Begins - 12:35AM21.7 ft. MWL - Water Level, 10 %of cross sectional area21.7 ft. MWM - Water Mark, 30 %of cross sectional area

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - MAG COAT 30% 8:00 TO 4:00 START

    2 ft. - General Observation - MAG COAT 30% 8:00 TO 4:00 START

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING-FLAKING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING-FLAKING CONCRETE

Observations (10)

DistanceCodeObservation
0AMH12:35AM
21.4SSSPEELING - FLAKING CONCRETE
0MWL
2SAVSEVERE AGG
0MWM
21.4SAVSEVERE AGG
2MGOMAG COAT 30% 8:00 TO 4:00 START
21.4MGOMAG COAT 30% FINISH
21.7AMH12:45AM
2SSSPEELING-FLAKING CONCRETE

Properties (6)

custom_field_three
THIN PEELING CONCRETE-VISIBLE SEVERE AGG
custom_field_two
3
customer
LACSD
datetime
2016-10-27T00:34:14-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false