Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 19, 2016, 11:53 AM
Date
10/19/2016
W/O
0596932
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00236
PipeID
P04167
Time
4:53 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6741
Sewer Name
02 ATLANTIC AVENUE RELIEF TRUNK
City
LOS ANGLES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Routine Assessment
Project
20161018MDM_ATALANTIC_AVENUE_RELIEF_TRUNK
Material
NRCP
Shape
Circular
Height
18 in.
Upstream MH
02 1820
Downstream MH
02 1819
Dir. of Survey
Downstream
Length Surveyed
350.7 ft.
Total Length
350.7 ft.
Structural Index
3
Structural Quick
4M2M
Structural Rating
426
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
426
Pipe schematic from manhole 02 1820 to 02 1819
MH: 02 1820MH: 02 1819downstream0 ft. AMH - Upstream Manhole, Survey Begins - 5:00AM0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. MGO - General Observation - MAG COAT 40% 8:00 TO 4:00 START2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE77.4 ft. MGO - General Observation - MAG COAT 30% START86 ft. MGP - General Photograph - PEELING CONCRETE & SEVERE AGG86 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED346.4 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - MISSING SEVERE AGG350.3 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG350.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - PEELING CONCRETE350.3 ft. MGO - General Observation - MAG COAT 30% FINISH350.7 ft. AMH - Downstream Manhole, Survey Ends - 5:30AM

Observation photos (7)

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - MAG COAT 40% 8:00 TO 4:00 START

    2 ft. - General Observation - MAG COAT 40% 8:00 TO 4:00 START

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE

  • General Observation - MAG COAT 30% START

    77.4 ft. - General Observation - MAG COAT 30% START

  • General Photograph - PEELING CONCRETE & SEVERE AGG

    86 ft. - General Photograph - PEELING CONCRETE & SEVERE AGG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

    86 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - MISSING SEVERE AGG

    346.4 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - MISSING SEVERE AGG

Observations (14)

DistanceCodeObservation
2SAMSEVERE AGG
346.4SAMMISSING SEVERE AGG
350.3SAMSEVERE AGG
86MGPPEELING CONCRETE & SEVERE AGG
86SSSPEELING CONCRETE SEVERE AGG ATTACHED
77.4MGOMAG COAT 30% START
350.3SSSPEELING CONCRETE
2MGOMAG COAT 40% 8:00 TO 4:00 START
0AMH5:00AM
350.7AMH5:30AM
350.3MGOMAG COAT 30% FINISH
2SSSPEELING CONCRETE
0MWM
0MWL

Properties (6)

custom_field_three
PEELING CONCRETE - MISSING SEVERE AGG
custom_field_two
2
customer
LACSD
datetime
2016-10-19T04:53:44-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection