Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 17, 2016, 07:50 AM
  • 22 0539A_22 0539_10172016_022019.mp4

Date
10/17/2016
W/O
0591578
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00791
PipeID
P16882
Time
12:50 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
HO325
Sewer Name
22 BEN LOMOND TRUNK
City
COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
20
Purpose
Routine Assessment
Project
20161015MDM_BEN_LOMOND_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
22 0539A
Downstream MH
22 0539
Dir. of Survey
Downstream
Length Surveyed
136.7 ft.
Total Length
136.7 ft.
Structural Index
2
Structural Quick
2500
Structural Rating
10
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
12
Pipe schematic from manhole 22 0539A to 22 0539
MH: 22 0539AMH: 22 0539downstream0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:15AM0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start0 ft. MWL - Water Level, 10 %of cross sectional area3.2 ft. JSL - Joint Separated Large - SEALED CUT JOINT6.5 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - HAIRLINE7.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped12.5 ft. MGO - General Observation - 8" VCP32.7 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H57 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped88.8 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - H88.8 ft. FC - Fracture Circumferential, from 12 to 01 o'clock, within 8 inches of joint: YES - SLIGHT103.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped136.3 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Capped136.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish136.7 ft. AMH - Downstream Manhole, Survey Ends - 2:30AM

Observation photos (2)

  • Joint Separated Large - SEALED CUT JOINT

    3.2 ft. - Joint Separated Large - SEALED CUT JOINT

  • General Observation - 8" VCP

    12.5 ft. - General Observation - 8" VCP

Observations (17)

DistanceCodeObservation
57TFCCapped
0MGOConn. @ Mh, 3 O' Clock. Active
0MWM
0AMH2:15AM
88.8FCH
3.2JSLSEALED CUT JOINT
32.7FCH
88.8FCSLIGHT
6.5FCHAIRLINE
12.5MGO8" VCP
103.3TFCCapped
136.3MGOConn. @ Mh, 3 O' Clock. Capped
0DAGS
7.7TFCCapped
0MWL
136.3DAGS
136.7AMH2:30AM

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2016-10-17T00:50:53-07:00
documentation
MARTIN,MANANES,OLIVER 111
is_lateral_inspection
false