Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 17, 2016, 07:49 AM
  • 22 0540_22 0539A_10172016_014624.mp4

Date
10/17/2016
W/O
0591578
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00791
PipeID
P24964
Time
12:49 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
HO325
Sewer Name
22 BEN LOMOND TRUNK
City
COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
20
Purpose
Routine Assessment
Project
20161015MDM_BEN_LOMOND_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
22 0540
Downstream MH
22 0539A
Dir. of Survey
Downstream
Length Surveyed
212.5 ft.
Total Length
212.5 ft.
Structural Index
2
Structural Quick
3126
Structural Rating
15
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
17
Pipe schematic from manhole 22 0540 to 22 0539A
MH: 22 0540MH: 22 0539Adownstream0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:30AM2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start6.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open9.1 ft. MGO - General Observation - 8" VCP19.2 ft. FC - Fracture Circumferential, from 08 to 01 o'clock, within 8 inches of joint: YES - HAIRLINE26 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H33.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped46 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H63.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped65.6 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - H66.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped68 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - H98.4 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SLIGHT112.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped115.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped147.3 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - H165.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped171.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped212 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active212 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish212.5 ft. AMH - Downstream Manhole, Survey Ends - 2:00AM

Observation photos (1)

  • General Observation - 8" VCP

    9.1 ft. - General Observation - 8" VCP

Observations (24)

DistanceCodeObservation
147.3FCH
212MGOConn. @ Mh, 3 O' Clock. Active
115.4TFCCapped
26FCH
6.9TFOpen
0MGOConn. @ Mh, 3 O' Clock. Active
63.7TFCCapped
65.6FCH
0MWM
66.2TFCCapped
165.3TFCCapped
68FCH
112.7TFCCapped
0MWL
212.5AMH2:00AM
33.7TFCCapped
0AMH1:30AM
46FLH
212DAGS
19.2FCHAIRLINE
9.1MGO8" VCP
2DAGS
98.4FCSLIGHT
171.1TFCCapped

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2016-10-17T00:49:08-07:00
documentation
MARTIN,MANANES,OLIVER 111
is_lateral_inspection
false