Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 7, 2016, 08:36 AM
  • C 0575_C 0641_1072016_043809.mp4

Date
10/07/2016
W/O
0592184
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00365
PipeID
P05122
Time
1:36 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0315
Sewer Name
C JOINT OUTFALL C - UNIT 4C RELIEF
City
LONG BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
16
Purpose
Routine Assessment
Project
20161007MDM_JOINT_OUTFALL_C_UNIT_4C_RELIEF
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Upstream MH
C 0575
Downstream MH
C 0641
Dir. of Survey
Downstream
Length Surveyed
179 ft.
Total Length
179 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole C 0575 to C 0641
MH: C 0575MH: C 0641downstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:35AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. MGO - General Observation - 36" RCP - CIPP2.8 ft. MGO - General Observation - WHITE BUILD-UP ON LINER149.8 ft. LFW - Lining Failure Wrinkled, from 03 to 04 o'clock, within 8 inches of joint: NO179 ft. AMH - Downstream Manhole, Survey Ends - 4:55AM

Observation photos (3)

  • General Observation - 36" RCP - CIPP

    2 ft. - General Observation - 36" RCP - CIPP

  • General Observation - WHITE BUILD-UP ON LINER

    2.8 ft. - General Observation - WHITE BUILD-UP ON LINER

  • Lining Failure Wrinkled, from 03 to 04 o'clock, within 8 inches of joint: NO

    149.8 ft. - Lining Failure Wrinkled, from 03 to 04 o'clock, within 8 inches of joint: NO

Observations (7)

DistanceCodeObservation
0AMH4:35AM
0MWL
2.8MGOWHITE BUILD-UP ON LINER
149.8LFW
179AMH4:55AM
0MWM
2MGO36" RCP - CIPP

Properties (7)

custom_field_three
CIPP LINER
custom_field_two
4
customer
LACSD
datetime
2016-10-07T01:36:59-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false
lining
CIPP