Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 6, 2016, 03:54 PM
  • 02 1871_02 1870_1062016_090156.mp4

Date
10/06/2016
W/O
0596961
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00246
PipeID
P04229
Time
8:54 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0314
Sewer Name
02 DOUGLAS AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Capital Improvement Program Assesment
Project
20161006AM_DOUGLAS_AVENUE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
02 1870
Downstream MH
02 1871
Dir. of Survey
Upstream
Length Surveyed
130.6 ft.
Total Length
130.6 ft.
Structural Index
4
Structural Quick
5947
Structural Rating
87
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
4
Overall Quick
Overall Rating
89
Pipe schematic from manhole 02 1870 to 02 1871
MH: 02 1870MH: 02 1871upstream0 ft. AMH - Upstream Manhole, Survey Ends - 9:44 AM0.7 ft. MGO - General Observation - ROACHES INSIDE THE MH.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2 ft. MGO - General Observation - SAGS THROUGHOUT THE REACH2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2 ft. MGO - General Observation - BROKEN PIPE5.9 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN7.2 ft. B - Broken, from 08 to 01 o'clock, within 8 inches of joint: YES48.1 ft. JOL - Joint Offset Large63.6 ft. B - Broken, from 10 to 02 o'clock, within 8 inches of joint: YES66.1 ft. B - Broken, from 10 to 03 o'clock, within 8 inches of joint: YES68.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start71.2 ft. B - Broken, from 12 to 04 o'clock, within 8 inches of joint: YES77.8 ft. TFD - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN, BROKEN78.8 ft. B - Broken, from 10 to 11 o'clock, within 8 inches of joint: YES83.9 ft. B - Broken, from 08 to 11 o'clock, within 8 inches of joint: YES89 ft. FM - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN91.7 ft. B - Broken, from 08 to 10 o'clock, within 8 inches of joint: YES96.7 ft. B - Broken, from 08 to 02 o'clock, within 8 inches of joint: YES99.3 ft. FM - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES104.3 ft. FM - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES109.6 ft. FM - Fracture Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN112.1 ft. FL - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES112.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start114.6 ft. B - Broken, from 10 to 02 o'clock, within 8 inches of joint: YES118.2 ft. CM - Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES119.2 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN120.8 ft. CM - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES123 ft. B - Broken, from 08 to 11 o'clock, within 8 inches of joint: YES126 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES130.6 ft. MGO - General Observation - CAPPED OFF CONN. INSIDE THE MH. @ 11 O'CLOCK130.6 ft. MWM - Water Mark, 15 %of cross sectional area130.6 ft. MWL - Water Level, 10 %of cross sectional area130.6 ft. AMH - Downstream Manhole, Survey Begins - 9:00 AM130.6 ft. MGO - General Observation - ROACHES INSIDE THE MH.

Observation photos (18)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    4.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Broken, from 08 to 11 o'clock, within 8 inches of joint: YES

    7.6 ft. - Broken, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Broken, from 10 to 02 o'clock, within 8 inches of joint: YES

    16 ft. - Broken, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES

    18.5 ft. - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

    21 ft. - Fracture Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

  • Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

    31.3 ft. - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Broken, from 08 to 02 o'clock, within 8 inches of joint: YES

    33.9 ft. - Broken, from 08 to 02 o'clock, within 8 inches of joint: YES

  • Broken, from 08 to 10 o'clock, within 8 inches of joint: YES

    38.9 ft. - Broken, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

    41.6 ft. - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

  • Broken, from 08 to 11 o'clock, within 8 inches of joint: YES

    46.7 ft. - Broken, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Broken, from 10 to 11 o'clock, within 8 inches of joint: YES

    51.8 ft. - Broken, from 10 to 11 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN, BROKEN

    52.8 ft. - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN, BROKEN

  • Broken, from 12 to 04 o'clock, within 8 inches of joint: YES

    59.4 ft. - Broken, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Broken, from 10 to 03 o'clock, within 8 inches of joint: YES

    64.5 ft. - Broken, from 10 to 03 o'clock, within 8 inches of joint: YES

  • Broken, from 10 to 02 o'clock, within 8 inches of joint: YES

    67 ft. - Broken, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Joint Offset Large

    82.5 ft. - Joint Offset Large

  • Broken, from 08 to 01 o'clock, within 8 inches of joint: YES

    123.4 ft. - Broken, from 08 to 01 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

    128.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observations (35)

DistanceCodeObservation
82.5JOL
0MGOCAPPED OFF CONN. INSIDE THE MH. @ 11 O'CLOCK
12.4CM
128.6FM
128.6MGOSAGS THROUGHOUT THE REACH
18.5FL
128.6CM
46.7B
38.9B
64.5B
61.9FM
0MWM
26.3FM
124.7TFOPEN
16B
0MWL
51.8B
4.6FM
11.4TFOPEN
0AMH9:00 AM
128.6MGOBROKEN PIPE
41.6FMPOSSIBLY BROKEN
123.4B
52.8TFDOPEN, BROKEN
33.9B
21FMPOSSIBLY BROKEN
18.5CM
7.6B
9.8CM
31.3FM
0MGOROACHES INSIDE THE MH.
59.4B
129.9MGOROACHES INSIDE THE MH.
67B
130.6AMH9:44 AM

Properties (7)

additional_info
RFIR INSPECTION
custom_field_three
BROKEN PIPE
custom_field_two
1
customer
LACSD
datetime
2016-10-06T08:54:38-07:00
documentation
MIRANDA, BRAR, SHADLER, FRANKLIN
is_lateral_inspection
false