Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 4, 2016, 09:07 AM
  • C 0659_C 0658_1042016_024730.mp4

Date
10/04/2016
W/O
0596966
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00266
PipeID
P23925
Time
2:07 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0308
Sewer Name
C JOINT OUTFALL C - UNIT 3F
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
01
Purpose
Routine Assessment
Project
20161004MDM_JOINT_OUTFALL_C_UNIT_3F
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
C 0658
Downstream MH
C 0659
Dir. of Survey
Upstream
Length Surveyed
335.8 ft.
Total Length
335.8 ft.
Structural Index
2
Structural Quick
382B
Structural Rating
51
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
53
Pipe schematic from manhole C 0658 to C 0659
MH: C 0658MH: C 0659upstream0 ft. AMH - Upstream Manhole, Survey Ends - 3:25AM0.2 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active11.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped29.3 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - S47.3 ft. FC - Fracture Circumferential, from 10 to 11 o'clock, within 8 inches of joint: YES - H52.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped80.9 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Open98.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped102.2 ft. JSM - Joint Separated Medium - SEALED105.8 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H122.3 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H132.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped133.1 ft. FC - Fracture Circumferential, from 11 to 04 o'clock, within 8 inches of joint: YES - H152.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped183.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped184.4 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H203.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped224.6 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H224.6 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H234.3 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H242.8 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H247.6 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H247.6 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H250.5 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SLIGHT250.5 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H252.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped254.7 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H254.9 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H285.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped290.7 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES290.7 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H305.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped316.6 ft. MGO - General Observation - 18" VCP316.7 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - HAIRLINE316.7 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SLIGHT321.8 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - HAIRLINE327.8 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open 100% GREASE335.8 ft. MWM - Water Mark, 30 %of cross sectional area335.8 ft. MWL - Water Level, 5 %of cross sectional area335.8 ft. AMH - Downstream Manhole, Survey Begins - 2:40AM

Observation photos (2)

  • General Observation - 18" VCP

    19.2 ft. - General Observation - 18" VCP

  • Joint Separated Medium - SEALED

    233.6 ft. - Joint Separated Medium - SEALED

Observations (40)

DistanceCodeObservation
83.2TFCCapped
213.5FLH
85.3FCSLIGHT
306.5FCS
81.1FLH
8TFDOpen 100% GREASE
230FLH
19.1FCHAIRLINE
30.4TFCCapped
0MWM
88.2FLH
203.3TFCCapped
19.2MGO18" VCP
45.1CL
0MWL
132.7TFCCapped
202.7FCH
283.7TFCCapped
0AMH2:40AM
101.5FCH
288.5FCH
254.9TFOpen
152.1TFCCapped
50.6TFCCapped
80.9FCH
93FLH
111.2FCH
111.2FCH
335.8AMH3:25AM
19.1FCSLIGHT
183.6TFCCapped
85.3FCH
45.1FLH
151.4FLH
88.2FCH
14FLHAIRLINE
324TFCapped
237TFCCapped
335.6MGOConn. @ Mh, 3 O' Clock. Active
233.6JSMSEALED

Properties (6)

custom_field_three
FEW SLIGHT FRACTURES
custom_field_two
4
customer
LACSD
datetime
2016-10-04T02:07:49-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false