Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 7, 2019, 09:38 AM
  • 18 1097_18 0080 _06072019_024500.mp4

Date
06/07/2019
W/O
766605
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00698
PipeID
P13899
Time
2:38 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6561
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
WO_766605_TV18083_MAY2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 1097
Downstream MH
18 0080
Dir. of Survey
Downstream
Length Surveyed
22.7 ft.
Total Length
22.7 ft.
Structural Index
3
Structural Quick
3828
Structural Rating
40
O&M Index
2
O&M Quick
2400
O&M Rating
8
Overall Index
2
Overall Quick
Overall Rating
48
Pipe schematic from manhole 18 1097 to 18 0080
MH: 18 1097MH: 18 0080downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 10970 ft. MWL - Water Level, 0 %of cross sectional area0 ft. MGO - General Observation - CONN IN MH @ 9 O'CLOCK/ACTIVE0 ft. MWM - Water Mark, 20 %of cross sectional area1.8 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start1.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start19.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish19.8 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish21 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish21 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish22 ft. MGO - General Observation - ROACHES @ MH22 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish22.6 ft. MGO - General Observation - CONNECTION IN MH 3 OCLOCK/ACTIVE22.7 ft. AMH - Downstream Manhole, Survey Ends - 18 0080

Observation photos (2)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    1.8 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    1.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
1.8SAP
1.9DAGS
2SSS
22MGOROACHES @ MH
19.8DAGS
0AMH18 1097
2SSS
22.7AMH18 0080
21SSS
0MWL
19.8SAP
22.6MGOCONNECTION IN MH 3 OCLOCK/ACTIVE
22SSS
0MGOCONN IN MH @ 9 O'CLOCK/ACTIVE
2CM
0MWM
21CM

Properties (6)

additional_info
SC377684
custom_field_two
3
customer
LACSD
datetime
2019-06-07T02:38:39-07:00
documentation
PROPIPE
is_lateral_inspection
false