Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 7, 2019, 04:52 AM
  • 18 0075A_18 0075 _06062019_220109.mp4

Date
06/06/2019
W/O
766605
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00698
PipeID
P13891
Time
9:52 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6561
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
WO_766605_TV18083_MAY2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0075A
Downstream MH
18 0075
Dir. of Survey
Downstream
Length Surveyed
134.3 ft.
Total Length
134.3 ft.
Structural Index
3
Structural Quick
3D00
Structural Rating
78
O&M Index
2
O&M Quick
2D00
O&M Rating
52
Overall Index
3
Overall Quick
Overall Rating
130
Pipe schematic from manhole 18 0075A to 18 0075
MH: 18 0075AMH: 18 0075downstream0 ft. MGO - General Observation - CONNECTION IN MH 9 OCLOCK/ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 18 0075A0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 70% MAG2.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start87.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ACTIVE132 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish133 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish133 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 70%MAG134 ft. MGO - General Observation - ROACHES @ MH134.3 ft. AMH - Downstream Manhole, Survey Ends - 18 0075

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.8 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
0MGOCONNECTION IN MH 9 OCLOCK/ACTIVE
0AMH18 0075A
133SAV
2.8DAGS
87.7TBACTIVE
2SZ70% MAG
0MWM
2.8SAV
0MWL
134.3AMH18 0075
134MGOROACHES @ MH
132DAGS
133SZ70%MAG

Properties (6)

additional_info
SC377684
custom_field_two
3
customer
LACSD
datetime
2019-06-06T21:52:22-07:00
documentation
PROPIPE
is_lateral_inspection
false