Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 22, 2019, 08:01 AM
  • 18 0892_18 0891 _22072019_013818.mp4

Date
07/22/2019
W/O
771927
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00709
PipeID
P14743
Time
1:01 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5934
Sewer Name
18 SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
City
NORWALK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
26
Purpose
Routine Assessment
Project
WO_771927_TV18101_JUN2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
18 0892
Downstream MH
18 0891
Dir. of Survey
Downstream
Length Surveyed
625.4 ft.
Total Length
625.4 ft.
Structural Index
3
Structural Quick
3X2X
Structural Rating
622
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
628
Pipe schematic from manhole 18 0892 to 18 0891
MH: 18 0892MH: 18 0891downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 08920 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COAT THROUGHOUT306.1 ft. MGO - General Observation - SAG IN PIPE450.1 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, at 02 o'clock, , within 8 inches of joint: NO - RAGS622 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish625 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish625.4 ft. AMH - Downstream Manhole, Survey Ends - 18 0891

Observation photos (6)

  • Upstream Manhole, Survey Begins - 18 0892

    0 ft. - Upstream Manhole, Survey Begins - 18 0892

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    0 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COAT THROUGHOUT

    2 ft. - General Observation - MAG COAT THROUGHOUT

  • General Observation - SAG IN PIPE

    306.1 ft. - General Observation - SAG IN PIPE

  • Deposits Attached Other, 5 %of cross sectional area, at 02 o'clock,  , within 8 inches of joint: NO - RAGS

    450.1 ft. - Deposits Attached Other, 5 %of cross sectional area, at 02 o'clock, , within 8 inches of joint: NO - RAGS

Observations (11)

DistanceCodeObservation
306.1MGOSAG IN PIPE
625.4AMH18 0891
450.1DAZRAGS
625SSS
0AMH18 0892
2SAV
0MWL
2MGOMAG COAT THROUGHOUT
622SAV
0MWM
0SSS

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-07-22T01:01:25-07:00
documentation
PRO PIPE
is_lateral_inspection
false