Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 24, 2019, 07:34 AM
  • 18 0885_18 0884 _24072019_005522.mp4

Date
07/24/2019
W/O
771927
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00709
PipeID
P14736
Time
12:34 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5937
Sewer Name
18 SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
City
NORWALK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
31
Purpose
Routine Assessment
Project
WO_771927_TV18101_JUN2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
18 0885
Downstream MH
18 0884
Dir. of Survey
Downstream
Length Surveyed
607.8 ft.
Total Length
607.8 ft.
Structural Index
3
Structural Quick
5W3W
Structural Rating
1197
O&M Index
2
O&M Quick
2W00
O&M Rating
242
Overall Index
3
Overall Quick
Overall Rating
1439
Pipe schematic from manhole 18 0885 to 18 0884
MH: 18 0885MH: 18 0884downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 08851.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COAT THROUGHOUT2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start9 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start604.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish604.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish607 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish607 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish607.3 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK607.8 ft. AMH - Downstream Manhole, Survey Ends - 18 0884

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    0 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    1.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COAT THROUGHOUT

    2 ft. - General Observation - MAG COAT THROUGHOUT

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    9 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - CONNECTION AT MH 9 O'CLOCK

    607.3 ft. - General Observation - CONNECTION AT MH 9 O'CLOCK

Observations (14)

DistanceCodeObservation
0MWL
607DAGS
607SSS
1.1SSS
2MGOMAG COAT THROUGHOUT
0DAGS
607.3MGOCONNECTION AT MH 9 O'CLOCK
0MWM
604.1SAV
0AMH18 0885
2SAV
9SRV
604.1SRV
607.8AMH18 0884

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-07-24T00:34:13-07:00
documentation
PRO PIPE
is_lateral_inspection
false