Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 24, 2019, 07:15 AM
  • 32 0143_32 0142 _09242019_002959.mp4

Date
09/24/2019
W/O
787630
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19891
Time
12:15 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7009
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_787630_TV32048_SEP2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 0143
Downstream MH
32 0142
Dir. of Survey
Downstream
Length Surveyed
532.1 ft.
Total Length
532.1 ft.
Structural Index
3
Structural Quick
3T00
Structural Rating
318
O&M Index
2
O&M Quick
412T
O&M Rating
216
Overall Index
3
Overall Quick
Overall Rating
534
Pipe schematic from manhole 32 0143 to 32 0142
MH: 32 0143MH: 32 0142downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 01430 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2.3 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start530 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish530 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish532.1 ft. AMH - Downstream Manhole, Survey Ends - 32 0142

Observation photos (3)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
0MGOCOCKROACHES IN MANHOLE
2.3SAP
530DAGS
0MWM
0AMH32 0143
0MWL
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
530SAP
2DAGS
532.1AMH32 0142

Properties (6)

additional_info
SC378625
custom_field_two
2
customer
LACSD
datetime
2019-09-24T00:15:28-07:00
documentation
PRO PIPE
is_lateral_inspection
false