Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 27, 2019, 05:48 AM
  • 32 0132_32 0131A_09262019_225927.mp4

Date
09/26/2019
W/O
787630
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19879
Time
10:48 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7018
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_787630_TV32048_SEP2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
32 0132
Downstream MH
32 0131A
Dir. of Survey
Downstream
Length Surveyed
276.4 ft.
Total Length
276.4 ft.
Structural Index
3
Structural Quick
3J2J
Structural Rating
275
O&M Index
2
O&M Quick
412J
O&M Rating
114
Overall Index
2
Overall Quick
Overall Rating
389
Pipe schematic from manhole 32 0132 to 32 0131A
MH: 32 0132MH: 32 0131Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 01320 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start274.6 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish274.6 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish274.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish276.4 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK276.4 ft. AMH - Downstream Manhole, Survey Ends - 32 0131A276.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (4)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    276.4 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (12)

DistanceCodeObservation
274.6SAP
0AMH32 0132
274.6SSS
276.4MGOACTIVE CONNECTION AT MH 3 O'CLOCK
2SSS
2SAP
2DAGS
274.6DAGS
0MWM
0MWL
276.4AMH32 0131A
276.4MGOCOCKROACHES IN MANHOLE

Properties (6)

additional_info
SC378634
custom_field_two
2
customer
LACSD
datetime
2019-09-26T22:48:14-07:00
documentation
PRO PIPE
is_lateral_inspection
false