Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 6, 2019, 04:59 AM
  • H 0335_H 0334 _05082019_221504.mp4

Date
08/05/2019
W/O
776936
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00175
PipeID
P10785
Time
9:59 PM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5952
Sewer Name
H JOINT OUTFALL H - UNIT 4
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
19A
Purpose
Routine Assessment
Project
RFIR_WO_776936_TV02325_JUL2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
63 in.
Width
63 in.
Upstream MH
H 0335
Downstream MH
H 0334
Dir. of Survey
Downstream
Length Surveyed
345.1 ft.
Total Length
345.1 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
7
Pipe schematic from manhole H 0335 to H 0334
MH: H 0335MH: H 0334downstream0 ft. AMH - Upstream Manhole, Survey Begins - H 03350 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. MWL - Water Level, 40 %of cross sectional area2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.2 ft. MGO - General Observation - MAG COAT THROUGHOUT342 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish345.1 ft. AMH - Downstream Manhole, Survey Ends - H 0334

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COAT THROUGHOUT

    2.2 ft. - General Observation - MAG COAT THROUGHOUT

Observations (7)

DistanceCodeObservation
2.1SAP
0AMHH 0335
342SAP
345.1AMHH 0334
2.2MGOMAG COAT THROUGHOUT
0MWM
0MWL

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-08-05T21:59:48-07:00
documentation
PRO PIPE
is_lateral_inspection
false