Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 20, 2019, 04:02 PM
  • H 0331_H 0330 _20082019_090930.mp4

Date
08/20/2019
W/O
766936
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z00175
PipeID
P10781
Time
9:02 AM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6787
Sewer Name
H JOINT OUTFALL H - UNIT 4
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_776936_TV02325_JUL2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Width
57 in.
Upstream MH
H 0331
Downstream MH
H 0330
Dir. of Survey
Downstream
Length Surveyed
155.5 ft.
Total Length
155.5 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole H 0331 to H 0330
MH: H 0331MH: H 0330downstream0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 03310 ft. MWM - Water Mark, 40 %of cross sectional area2.5 ft. MGO - General Observation - MAG COAT THROUGHOUT2.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start152.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish152.7 ft. VC - Vermin Cockroach155.5 ft. AMH - Downstream Manhole, Survey Ends - H 0330

Observation photos (2)

  • General Observation - MAG COAT THROUGHOUT

    2.5 ft. - General Observation - MAG COAT THROUGHOUT

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
152.7SAP
152.7VC
0MWL
155.5AMHH 0330
2.5MGOMAG COAT THROUGHOUT
2.5SAP
0AMHH 0331
0MWM

Properties (6)

additional_info
SC378293
custom_field_two
3
customer
LACSD
datetime
2019-08-20T09:02:42-07:00
documentation
PRO PIPE
is_lateral_inspection
false