Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 3, 2019, 05:50 AM
  • 32 0120_32 0119A_10022019_230253.mp4

Date
10/02/2019
W/O
787483
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P25788
Time
10:50 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7027
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
08
Purpose
Routine Assessment
Project
WO_787483_TV32016_SEP2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
32 0120
Downstream MH
32 0119A
Dir. of Survey
Downstream
Length Surveyed
123.2 ft.
Total Length
123.2 ft.
Structural Index
3
Structural Quick
563B
Structural Rating
119
O&M Index
2
O&M Quick
2D00
O&M Rating
48
Overall Index
3
Overall Quick
Overall Rating
167
Pipe schematic from manhole 32 0120 to 32 0119A
MH: 32 0120MH: 32 0119Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 01200 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start24 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start34.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start46.8 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO98.6 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start121.3 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish121.3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish121.3 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish121.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish123.2 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK123.2 ft. AMH - Downstream Manhole, Survey Ends - 32 0119A123.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    24 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    34.2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO

    46.8 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

    98.6 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    123.2 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (16)

DistanceCodeObservation
121.3SAP
0AMH32 0120
123.2MGOACTIVE CONNECTION AT MH 9 O'CLOCK
123.2AMH32 0119A
0MWL
121.3SSS
0MWM
46.8SRV
123.2MGOCOCKROACHES IN MANHOLE
98.6SRV
24SSS
121.3SRV
2DAGS
34.2SAP
0MGOCOCKROACHES IN MANHOLE
121.3DAGS

Properties (6)

additional_info
SC378644
custom_field_two
2
customer
LACSD
datetime
2019-10-02T22:50:56-07:00
documentation
PRO PIPE
is_lateral_inspection
false