Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 3, 2019, 08:41 AM
  • 32 0136_32 1268_10032019_015231.mp4

Date
10/03/2019
W/O
787483
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P20560
Time
1:41 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7027
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
09
Purpose
Routine Assessment
Project
WO_787483_TV32016_SEP2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
32 0136
Downstream MH
32 1268
Dir. of Survey
Downstream
Length Surveyed
100.9 ft.
Total Length
100.9 ft.
Structural Index
3
Structural Quick
3C2C
Structural Rating
100
O&M Index
2
O&M Quick
4138
O&M Rating
68
Overall Index
2
Overall Quick
Overall Rating
168
Pipe schematic from manhole 32 0136 to 32 1268
MH: 32 0136MH: 32 1268downstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 01360 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 70 %of cross sectional area0 ft. MWL - Water Level, 40 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start2.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start59.4 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS100.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Finish100.8 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish100.8 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 AND 9 O'CLOCK100.8 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish100.8 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish100.9 ft. AMH - Downstream Manhole, Survey Ends - 32 1268100.9 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    100.9 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (16)

DistanceCodeObservation
100.8DAGS
100.9AMH32 1268
2DAGS
100.8SAP
2.2SAP
0AMH32 0136
59.4DSZDEBRIS
2.2SSS
0MGOCOCKROACHES IN MANHOLE
100.8MGOACTIVE CONNECTION AT MH 3 AND 9 O'CLOCK
100.8DSZ
100.8SSS
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
100.9MGOCOCKROACHES IN MANHOLE
0MWM
0MWL

Properties (6)

additional_info
SC378644
custom_field_two
2
customer
LACSD
datetime
2019-10-03T01:41:44-07:00
documentation
PRO PIPE
is_lateral_inspection
false