Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 26, 2019, 05:36 AM
  • 32 0126_32 0163_09252019_224839.mp4

Date
09/25/2019
W/O
787483
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19872
Time
10:36 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7015
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
08
Purpose
Routine Assessment
Project
WO_787483_TV32016_SEP2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
32 0126
Downstream MH
32 0163
Dir. of Survey
Downstream
Length Surveyed
64.1 ft.
Total Length
64.1 ft.
Structural Index
4
Structural Quick
5A3A
Structural Rating
96
O&M Index
2
O&M Quick
2A00
O&M Rating
24
Overall Index
3
Overall Quick
Overall Rating
120
Pipe schematic from manhole 32 0126 to 32 0163
MH: 32 0126MH: 32 0163downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 01260 ft. MWL - Water Level, 25 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start7 ft. MGP - General Photograph - HOLE7.1 ft. HSV - Hole Soil Visible, from 12 to 03 o'clock, within 8 inches of joint: YES7.3 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start61.9 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish61.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish61.9 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish61.9 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK64.1 ft. AMH - Downstream Manhole, Survey Ends - 32 016364.1 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Photograph - HOLE

    7 ft. - General Photograph - HOLE

  • Hole Soil Visible, from 12 to 03 o'clock, within 8 inches of joint: YES

    7.1 ft. - Hole Soil Visible, from 12 to 03 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    7.3 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
2SAP
61.9SAP
61.9DAGS
0MGOCOCKROACHES IN MANHOLE
7MGPHOLE
7.1HSV
7.3SRV
64.1AMH32 0163
64.1MGOACTIVE CONNECTION AT MH 9 O'CLOCK
2DAGS
61.9SRV
0MWM
61.9MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0AMH32 0126
0MWL

Properties (7)

additional_info
SC378630
custom_field_two
2
customer
LACSD
datetime
2019-09-25T22:36:05-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
26793