Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 17, 2019, 08:40 AM
  • 02 1609_02 1608_17072019_022957.mp4

Date
07/17/2019
W/O
777261
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00230
PipeID
P04013
Time
1:40 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5931
Sewer Name
02 ARIZONA AVENUE TRUNK, SECTION 1
City
E LOS ANGELES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
08
Purpose
Routine Assessment
Project
WO_777261_TV02003_JUL2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
02 1608
Downstream MH
02 1609
Dir. of Survey
Upstream
Length Surveyed
98.5 ft.
Total Length
98.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2C00
O&M Rating
38
Overall Index
2
Overall Quick
Overall Rating
38
Pipe schematic from manhole 02 1608 to 02 1609
MH: 02 1608MH: 02 1609upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 16091.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish8 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8"96.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start98.5 ft. MWL - Water Level, 20 %of cross sectional area98.5 ft. AMH - Downstream Manhole, Survey Begins - 02 160898.5 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED98.5 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK98.5 ft. MWM - Water Mark, 40 %of cross sectional area

Observation photos (3)

  • General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED

    0 ft. - General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED

  • General Observation - CONNECTION AT MH 9 O'CLOCK

    0 ft. - General Observation - CONNECTION AT MH 9 O'CLOCK

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8"

    90.5 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8"

Observations (9)

DistanceCodeObservation
0MWL
0AMH02 1608
97DAGS
0MGOCONNECTION AT MH 9 O'CLOCK CAPPED
0MGOCONNECTION AT MH 9 O'CLOCK
90.5TB
2DAGS
98.5AMH02 1609
0MWM

Properties (7)

custom_field_two
4
customer
LACSD
datetime
2019-07-17T01:40:13-07:00
documentation
PRO PIPE
is_lateral_inspection
false
lining
CIPP
year_laid
38526