Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 22, 2019, 11:00 AM
  • 08 0227_08 0226_22072019_041353.mp4

Date
07/22/2019
W/O
776944
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00005
PipeID
P00101
Time
4:00 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6718
Sewer Name
08 EAST ROAD TRUNK
City
TORRANCE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_776944_TV08112_JUL2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
08 0227
Downstream MH
08 0226
Dir. of Survey
Downstream
Length Surveyed
139 ft.
Total Length
139 ft.
Structural Index
4
Structural Quick
4231
Structural Rating
11
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
13
Pipe schematic from manhole 08 0227 to 08 0226
MH: 08 0227MH: 08 0226downstream0 ft. AMH - Upstream Manhole, Survey Begins - 08 02270 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH0 ft. MWL - Water Level, 20 %of cross sectional area5.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start7.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start45.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"54.7 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"66.1 ft. FH2 - Fracture Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Start86.7 ft. FM - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES116.1 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"135.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish135.1 ft. FH2 - Fracture Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish135.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish139 ft. AMH - Downstream Manhole, Survey Ends - 08 0226139 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    5.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    66.1 ft. - Fracture Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    86.7 ft. - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

Observations (16)

DistanceCodeObservation
5.5DAGS
0AMH08 0227
139AMH08 0226
7.5CM
66.1FH2
0MWM
0MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
135.1CM
45.7TFC
0MWL
139MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
116.1TFA
54.7TB
135.1FH2
86.7FM
135.1DAGS

Properties (6)

additional_info
SC378217
custom_field_two
3
customer
LACSD
datetime
2019-07-22T04:00:22-07:00
documentation
PROPIPE
is_lateral_inspection
false