Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 19, 2019, 09:23 AM
  • 18 0933_18 0932 _19072019_023044.mp4

Date
07/19/2019
W/O
776859
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00700
PipeID
P14781
Time
2:23 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6641
Sewer Name
18 SCOTT AVENUE TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_776859_TV18118_JUL2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
18 0933
Downstream MH
18 0932
Dir. of Survey
Downstream
Length Surveyed
85.7 ft.
Total Length
85.7 ft.
Structural Index
3
Structural Quick
463A
Structural Rating
54
O&M Index
2
O&M Quick
412B
O&M Rating
36
Overall Index
3
Overall Quick
Overall Rating
90
Pipe schematic from manhole 18 0933 to 18 0932
MH: 18 0933MH: 18 0932downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 09332 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start4.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start14.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"22.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"33.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start33.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish71.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"74.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"83.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish83.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish85.7 ft. AMH - Downstream Manhole, Survey Ends - 18 093285.7 ft. MGO - General Observation - COCKROACHES IN MANHOLE85.7 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    33.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    85.7 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (16)

DistanceCodeObservation
71.7TFC
0MWM
83.7DAGS
85.7AMH18 0932
0MWL
4.2FM
33.9CM
2DAGS
22.9TFA
83.7CM
85.7MGOCOCKROACHES IN MANHOLE
74.6TFC
14.3TFC
33.9FM
85.7MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0AMH18 0933

Properties (6)

additional_info
SC378308
custom_field_two
2
customer
LACSD
datetime
2019-07-19T02:23:24-07:00
documentation
PRO PIPE
is_lateral_inspection
false