- Date
- 07/19/2019
- W/O
- 776859
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00700
- PipeID
- P14781
- Time
- 2:23 AM
- Certificate
- U-111-11880
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K6641
- Sewer Name
- 18 SCOTT AVENUE TRUNK
- City
- WHITTIER
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 18
- Page No.
- 21
- Purpose
- Routine Assessment
- Project
- RFIR_WO_776859_TV18118_JUL2019
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 8 in.
- Width
- 8 in.
- Upstream MH
- 18 0933
- Downstream MH
- 18 0932
- Dir. of Survey
- Downstream
- Length Surveyed
- 85.7 ft.
- Total Length
- 85.7 ft.
- Structural Index
- 3
- Structural Quick
- 463A
- Structural Rating
- 54
- O&M Index
- 2
- O&M Quick
- 412B
- O&M Rating
- 36
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 90
Pipe schematic from manhole 18 0933 to 18 0932 Observation photos (4)

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

4.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

33.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

85.7 ft. - General Observation - COCKROACHES IN MANHOLE