Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 8, 2017, 08:56 AM
  • 05 1355_05 1354 _11082017_005649.mp4

Date
11/08/2017
W/O
668908
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00444
PipeID
P06571
Time
12:56 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5213
Sewer Name
05 GARDENA PUMP TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
21
Purpose
Routine Assessment
Project
WO_668908_TV05031_NOV2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 1355
Downstream MH
05 1354
Dir. of Survey
Downstream
Length Surveyed
42.9 ft.
Total Length
42.9 ft.
Structural Index
3
Structural Quick
3800
Structural Rating
24
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
24
Pipe schematic from manhole 05 1355 to 05 1354
MH: 05 1355MH: 05 1354downstream0 ft. MGO - General Observation - MAG COATING 75%0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 13552 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start8.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"40.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish42.9 ft. AMH - Downstream Manhole, Survey Ends - 05 135442.9 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0MGOMAG COATING 75%
0MWL
2SAP
40.5SAP
42.9AMH05 1354
42.9MGOCOCKROACHES IN MANHOLE
8.9TFC
0AMH05 1355

Properties (6)

additional_info
SC346084
custom_field_two
2
customer
LACSD
datetime
2017-11-08T00:56:28-08:00
documentation
PRO PIPE
is_lateral_inspection
false