- Date
- 09/27/2019
- W/O
- 0787705
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00098
- PipeID
- P09025
- Time
- 4:49 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- I0253
- Sewer Name
- B JOINT OUTFALL B - UNIT 6D
- City
- ROSEMEAD
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 15
- Page No.
- 20
- Purpose
- Capital Improvement Program Assesment
- Project
- 20190924MDM_JOINT_OUTFALL_B_UNIT_6D
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 36 in.
- Upstream MH
- B 0868
- Downstream MH
- B 0484
- Dir. of Survey
- Downstream
- Length Surveyed
- 474.7 ft.
- Total Length
- 474.7 ft.
- Structural Index
- 3
- Structural Quick
- 3R2R
- Structural Rating
- 476
- O&M Index
- 4
- O&M Quick
- 4100
- O&M Rating
- 4
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 480
Pipe schematic from manhole B 0868 to B 0484 Observation photos (6)

2 ft. - General Observation - MAG COAT 80% START

2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE

53.7 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

140.5 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

459.7 ft. - Water Mark, 70 %of cross sectional area