Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 27, 2019, 11:01 AM
  • Section#14_B 0869_B 0868__9272019__I0253.mp4

Date
09/27/2019
W/O
0787705
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00098
PipeID
P09026
Time
4:01 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0253
Sewer Name
B JOINT OUTFALL B - UNIT 6D
City
ROSEMEAD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
20
Purpose
Capital Improvement Program Assesment
Project
20190924MDM_JOINT_OUTFALL_B_UNIT_6D
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Upstream MH
B 0869
Downstream MH
B 0868
Dir. of Survey
Downstream
Length Surveyed
616.1 ft.
Total Length
616.1 ft.
Structural Index
3
Structural Quick
3X2X
Structural Rating
624
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
624
Pipe schematic from manhole B 0869 to B 0868
MH: B 0869MH: B 0868downstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:10AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. MGO - General Observation - MAG COAT 50% START2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE123.2 ft. MWM - Water Mark, 40 %of cross sectional area135.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG156.7 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG UNDER MAG COAT321.4 ft. MWM - Water Mark, 30 %of cross sectional area522.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG534.8 ft. MGO - General Observation - 80% MAG COAT616.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING FLAKING CONCRETE616.1 ft. MGO - General Observation - MAG COAT 80% FINISH616.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG616.1 ft. AMH - Downstream Manhole, Survey Ends - 4:45AM

Observation photos (7)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - MAG COAT 50% START

    2 ft. - General Observation - MAG COAT 50% START

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE  AGG

    135.6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG UNDER MAG COAT

    156.7 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG UNDER MAG COAT

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    522.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • General Observation - 80% MAG COAT

    534.8 ft. - General Observation - 80% MAG COAT

Observations (16)

DistanceCodeObservation
2SAPSEVERE AGG
616.1SSSBLISTERING FLAKING CONCRETE
2MGOMAG COAT 50% START
616.1MGOMAG COAT 80% FINISH
156.7SAPSEVERE AGG UNDER MAG COAT
534.8MGO80% MAG COAT
522.1SAPSEVERE AGG
616.1SAPSEVERE AGG
0AMH4:10AM
135.6SAPSEVERE AGG
321.4MWM
0MWL
0MWM
2SSSBLISTERING FLAKING CONCRETE
616.1AMH4:45AM
123.2MWM

Properties (6)

custom_field_three
SEVERE AGG PROJECTING
custom_field_two
3
customer
LACSD
datetime
2019-09-27T04:01:30-07:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false